Replacing Parts

975-0320-01-01

6–7

3. Using an insulated screwdriver, disconnect the PV NEGATIVE (–) wire from

the terminal block inside the inverter. Cap the wire immediately with a wire
nut.

4. Disconnect the remaining AC, DC and network cables between the inverter

and the wiring box, inside the inverter. Cap all disconnected AC and DC wires
with wire nuts.

5. Inside the inverter, remove the four nuts attaching the wiring box to the

inverter. See Figure 6-3.

6. Push the connecting DC and AC wires down inside the wiring box.

7. Lift the inverter off the mounting bracket, leaving the wiring box in place.

8. Ensure the gasket on the wiring/disconnect box is clean and undamaged. The

gasket must create a water-tight seal between the inverter and
wiring/disconnect box.

Figure 6-3 Wiring/Disconnect Box and Removable Inverter

Four nuts to
secure inverter

Gasket