Front panel display screens and what they mean, Startup mode – Xantrex Technology GT5.0-NA User Manual

Page 50

Advertising
background image

Monitoring the Inverter

5–2

975-0320-01-01

Viewing more
information

Additional screens of information about the performance of the GT Inverter can be
displayed by tapping the Xantrex logo on the inverter front panel. This causes the
LCD to cycle through a series of information screens in Normal Operation,
Offline or Fault modes. These are described in detail in the following section,
“Front Panel Display Screens and What They Mean”.

Front Panel Display Screens and What They Mean

The front panel display shows different message screens during different modes of
operation (Startup, Normal, Offline, and Fault). All single units display a basic set
of message screens; multiple unit systems display additional screens in Normal
Operation and Offline modes.

In addition there are Special message screens that may appear in any operational
mode. All these message screens are described in more detail in the following
tables.

Startup Mode

During startup, the GT Inverter displays several message screens on its front panel
LCD. These screens appear in the following order (Table 5-1).

Table 5-1 Startup Screens on GT Inverter Front Panel Display

Display

Duration

Description

Power 5000W

Region NA-240V

5 seconds Startup message 1: Maximum output power and

Region-nominal output voltage

Flash = 03.00

..

ROM = 03.00

5 seconds Startup message 2: Model and revision numbers

for Flash and ROM memory on the GT Inverter.
The ROM revision number applies to the
protection processor.

Vh=

261V

Clr t < 1.00s

3 seconds Vh: phase-to-phase (rms) high threshold voltage

setting, the threshold at which the inverter
disconnects itself from the power grid when
abnormally high phase-to-phase AC voltage is
detected.*
Clr t: clear time.†

Vl=

214V

Clr t < 2.00s

3 seconds Vl: phase-to-phase (rms) low threshold voltage

setting, the threshold at which the inverter
disconnects itself from the power grid when
abnormally low phase-to-phase AC voltage is
detected.
Clr t: clear time.