Xantrex Technology GT5.0-NA User Manual

Page 46

Advertising
background image

Starting the Inverter

4–4

975-0320-01-01

If the inverter stops operating after the input current has risen above 1 A, turn
the unit off, remove DC power, and have a certified electrician or technician
inspect the ground fault protection fuse. If the fuse has blown, a DC wiring
problem may exist. Check all DC wiring to ensure that the unit is connected to
a single PV array.

5. Proceed to the next inverter and perform the same test. See Figure 4-2 for an

example of the recommended commissioning sequence.

Figure 4-2 Commissioning Sequence for Multiple Inverters