York ECO2 YPAL 050 User Manual
Page 131

131
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
6
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
5
1 = W2 ON (HEATING 2ND STAGE)
6
1 = W3 ON (HEATING 3RD STAGE)
7
1 = G ON (INDOOR FAN)
15 L
21 L
NA
-
-
-
INPUT STATUS BYTE #2
0
1 = HPS1 CLOSED (NOT TRIPPED)
1
1 = HPS2 CLOSED
2
1 = HPS3 CLOSED
3
1 = HPS4 CLOSED
4
1 = LPS1 CLOSED (NOT TRIPPED)
5
1 = LPS2 CLOSED
6
1 = LPS3 CLOSED
7
1 = LPS4 CLOSED
16 H
22 H
NA
-
-
-
INPUT STATUS BYTE #3
0
1 = C1 OVERLOAD CLOSED (NOT TRIPPED)
1
1 = C2 OVERLOAD CLOSED
2
1 = C3 OVERLOAD CLOSED
3
1 = C4 OVERLOAD CLOSED
4
1 = PURGE SWITCH CLOSED (ACTIVE)
5
1 = OCC INPUT ON
6
NA
7
1 = DIRTY FILTER CLOSED (DIRTY CONDITION)
16 L
22 L
NA
-
-
-
INPUT STATUS BYTE #4
0
1 = GAS VALVE #1 ON
1
1 = GAS VALVE #2 ON
2
1 = GAS VALVE #3 ON
3
1 = LIMIT #1 CLOSED (NOT TRIPPED)
4
1 = LIMIT #2 CLOSED
5
1 = LIMIT #3 CLOSED
6
NA
7
NA
17 L
23 H
NA
-
-
-
INPUT STATUS BYTE #5
0
1 = FAN OVERLOAD CLOSED (NOT TRIPPED)
1
1 = FREEZE STAT CLOSED (NOT LOW TEMPERATURE)
2
1 = AIR PROVING CLOSED (AIR FLOW IS SENSED)
3
NA
4
NA
5
1 = VAV; 0 = CV
6
1 = CV / VAV OUT OF RANGE (FAULT CONDITION)
7
1 = LOW 24 VAC SUPPLY VOLTAGE
17 H
23 L
NA
-
-
-
INPUT STATUS BYTE #6
0
1 = PROGRAM BUTTON PRESSED
1
1 = TEST / UP BUTTON PRESSED
2
1 = ALARMS / CHANGE BUTTON PRESSED
Continued on next page
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)