Section 7 – parameter descriptions and options – York ECO2 YPAL 050 User Manual

Page 141

Advertising
background image

141

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

7

TABLE 7-1 – DEFINITIONS

Continued on next page

SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS

MENU ITEM

DEFINITION

ACCUMULATED UNOCCUPIED OVERRIDE TIME

THIS PARAMETER GIVES THE ACCUMULATED TIME THE UNIT

HAS PLACED IN UNOCCUPIED OVERRIDE MODE.

ACTIVE ALARM

THIS IDENTIFIES THE NUMBER OF ACTIVE ALARMS PRESENT

ADDRESS

THIS PARAMETER IS USED TO SET THE COMMUNICATION

ADDRESS FOR THE UNIT WHEN CONNECTED TO A NETWORK

APS DATA

THIS PARAMETER GIVES THE STATUS OF THE SUPPLY FAN AIR

PROVING SWITCH. 0 = SWITCH OPEN, 1 = SWITCH CLOSED

BUILDING PRESSURE SETPOINT

THIS PARAMETER ESTABLISHES THE BUILDING PRESSURE

SETPOINT FOR THE CONTROL OF BUILDING EXHAUST

OPERATION

BUILDING STATIC PRESSURE

THIS PARAMETER GIVES THE CURRENT VALUE OF THE

BUILDING STATIC PRESSURE INPUT

BUILDING STATIC PRESSURE SENSOR

INSTALLED

THIS PARAMETER MUST BE TURNED ON TO ENABLE THE USE

OF BUILDING PRESSURE IN THE OPERATION OF THE EXHAUST

FUNCTION

COMFORT VENTILATION FOR COOLING

ENABLED

THIS PARAMETER MUST BE TURNED ON TO ENABLED

COMFORT VENTILATION DURING COOLING MODE OPERATION

ON A CONSTANT VOLUME UNIT

COMFORT VENTILATION FOR HEATING

ENABLED

THIS PARAMETER MUST BE TURNED ON TO ENABLE COMFORT

VENTILATION DURING HEATING MODE OPERATION ON A

CONSTANT VOLUME UNIT

COMFORT VENTILATION LOWER SETPOINT

THIS PARAMETER IS THE LOWER SETPOINT USED BY THE UNIT

CONTROLLER TO DETERMINE WHEN TO SWITCH THE UNIT IN

COMFORT VENTILATION MODE

COMFORT VENTILATION UPPER SETPOINT

THIS PARAMETER IS THE UPPER SETPOINT USED BY THE UNIT

CONTROLLER TO DETERMINE WHEN TO SWITCH THE UNIT IN

COMFORT VENTILATION MODE

COMP 1 ASCD ACTIVE

THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE

TIMER. ON MEANS THE COMPRESSOR 1 IS IN THIS MODE

COMP 1 ASCD TIMER

THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR

COMPRESSOR 1 IN SECONDS.

COMP 1 MIN RUN TIME

THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR

COMPRESSOR 1 IN SECONDS.

COMP 1 OUTPUT

THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE

UNIT CONTROLLER TO COMPRESSOR CIRCUIT 1

COMP 1 OVERLOAD SWITCH

THIS IS THE STATUS OF THE BINARY INPUT FROM THE

COMPRESSOR OVERLOAD FOR COMPRESSOR SYSTEM 1 TO

THE UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

COMP 2 ASCD ACTIVE

THIS IS USED TO DETERMINE THE STATUS OF THE OFF CYCLE

TIMER. ON MEANS THE COMPRESSOR 2 IS IN THIS MODE

COMP 2 ASCD TIMER

THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR

COMPRESSOR 2 IN SECONDS.

COMP 2 MIN RUN TIME

THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME FOR

COMPRESSOR 2 IN SECONDS.