ELECTRICAL DATA

ELECTRICAL SERVICE SIZING

In order to use the electrical service required for
the cooling only eco2 rooftop, use the appropriate
calculations listed below from U.L. 1995. Based on the
confi guration of the rooftop, the calculations will yield
different MCA (minimum circuit ampacity), and MOP
(maximum overcurrent protection).
Using the following load defi nitions and calculations,
determine the correct electrical sizing for your unit. All
concurrent load conditions must be considered in the
calculations, and you must use the highest value for any
combination of loads.

Load Defi nitions:

LOAD1 is the current of the largest motor – com-

pressor or fan motor.

LOAD2 is the sum of the remaining motor cur-

rents that may run concurrently with LOAD1.

LOAD3 is the current of the electric heaters

– zero for cooling only units.

LOAD4 is the sum of any remaining currents

greater than or equal to 1.0 amp.

Use the following calculations to determine MCA
and MOP for units supplied with a single-point power
connection:

MCA = (1.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4

MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4

If the MOP does not equal a standard current rating
of an overcurrent protective device, then the marked
maximum rating is to be the next lower standard rating.
However, if the device selected for MOP is less than the
MCA, then select the lowest standard maximum fuse
size greater than or equal to the MCA.

TABLE 2-7 – COMPRESSOR DATA - R410A

MODEL

MODEL

NOMINAL VOLTAGE

208-230/3/60

460/3/60

575/3/60

RLA*

LRA

RLA*

LRA

RLA*

LRA

050

1A

ZP120

33.3

239

17.9

125

12.8

80

1B

ZP137

48.0

245

18.6

125

14.7

100

2A

ZP121

33.3

239

17.9

125

12.8

80

2B

ZP137

48.0

245

18.6

125

14.7

100

051

1A

ZP137

48.0

245

18.6

125

14.7

100

1B

ZP137

48.0

245

18.6

125

14.7

100

2A

ZP137

48.0

245

18.6

125

14.7

100

2B

ZP137

48.0

245

18.6

125

14.7

100

060

1A

ZP137

48.0

245

18.6

125

14.7

100

1B

ZP182

55.7

340

26.9

172

23.7

132

2A

ZP137

48.0

245

18.6

125

14.7

100

2B

ZP182

55.7

340

26.9

172

23.7

132

061

1A

ZP154

51.3

300

22.4

150

19.8

109

1B

ZP182

55.7

340

25.0

172

23.7

132

2A

ZP137

48.0

245

18.6

125

14.7

100

2B

ZP182

55.7

340

25.0

172

23.7

132

TABLE 2-8 – POWER SUPPLY VOLTAGE LIMITS

POWER SUPPLY

MINIMUM VOLTAGE

MAXIMUM VOLTAGE

208/230V/3PH/60HZ

187

253

460V/3PH/60HZ

414

506

575V/3PH/60HZ

518

632