User interface control center – York ECO2 YPAL 050 User Manual

Page 132

Advertising
background image

132

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

User Interface Control Center

TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)

Continued on next page

ADDRESS

(HEX)

ADDRESS

(DEC)

BIT

INITIAL/

DEFAULT

VALUE

(HEX)

MIN

VALUE

MAX

VALUE

DESCRIPTION

3

1 = ADDRESS / DOWN BUTTON PRESSED

4

NA

5

NA

6

NA

7

NA

18 H

24 H

NA

-

-

-

OUTPUT STATUS BYTE #1

0

1 = COMPRESSOR #1 ON

1

1 = COMPRESSOR #2 ON

2

1 = COMPRESSOR #3 ON

3

1 = COMPRESSOR #4 ON

4

1 = CONDENSER FAN #1 ON

5

1 = CONDENSER FAN #2 ON

6

1 = INDOOR FAN ON

7

1 = EXHAUST FAN ON

18 L

24 L

NA

-

-

-

OUTPUT STATUS BYTE #2

0

1 = STAGE 1 HEAT ON

1

1 = STAGE 2 HEAT ON

2

1 = STAGE 3 HEAT ON

3

NA

4

NA

5

NA

6

NA

7

NA

19 H

25 H

NA

-

-

-

OUTPUT STATUS BYTE #3

0

1 = COMPRESSORS OFF BECAUSE FREE COOLING IS AVAILABLE

1

1 = COMPRESSORS OFF BECAUSE OF LOW AMBIENT

2

1 = COMPRESSORS OFF BECAUSE SUPPLY VOLTAGE IS LOW

3

1 = CONTROL IS IN COMFORT VENTILATION MODE

4

1 = DISABLE CONTROL IS ACTIVE

5

1 = ECONOMIZER IS USING FREE COOLING

6

NA

7

NA

19 L

25 L

NA

-

-

-

OUTPUT STATUS BYTE #4

0

1 = COMPRESSOR #1 OFF BECAUSE OF ASCD

1

1 = COMPRESSOR #2 OFF BECAUSE OF ASCD

2

1 = COMPRESSOR #3 OFF BECAUSE OF ASCD

3

1 = COMPRESSOR #4 OFF BECAUSE OF ASCD

4

NA

5

NA

6

NA

7

NA

1A H

26 H

NA

12

-

-

OPTION BYTE #2