Unit weights, Installation – York ECO2 YPAL 050 User Manual

Page 20

Advertising
background image

20

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

Installation

TABLE 2-2 – UNIT WEIGHTS - 050-061 MODELS

MODEL SIZE

050

051

060

061

BASIC UNIT*

7433

7433

7800

7819

ECONOMIZERS

NO

OUTSIDE

AIR

240

240

240

240

25% OUTSIDE AIR FIXED POSITION MAUAL

DAMPER

446

446

446

446

25% OUTSIDE AIR 2 POSITION ACTUATED

DAMPER

476

476

476

476

FULL MODULATION WITH MINIMUM POSITION

476

476

476

476

POWER EXHAUSTS

FAN, MOTOR, MODULATING DAMPER AND HOOD

501

501

501

501

FAN, MOTOR, VFD, BAROMETRIC DAMPER AND

HOOD

506

506

506

506

GAS HEAT

375

MBH

162

162

162

162

750

MBH

324

324

324

324

1125

MBH

486

486

486

486

OPTIONS

OPEN PERIMETER CURB

544

544

544

544

CONDENSER COIL WIRE GUARD

64

64

64

64

COPPER CONDENSER COILS (ADDITIONAL)

516

516

773

773

12” RIGID FILTERS (ADDITIONAL)

319

319

319

319

*UNIT INCLUDES FC FAN W/ 20 HP MOTOR, VFD AND 2” THROWAWAY FILTERS

X

339

Y

92

A

B C

D

Condenser
Coil End

Center of Gravity

TABLE 2-3 – UNIT CENTER OF GRAVITY

MODEL

050

051

X

Y

X

Y

BASIC UNIT

184.1

50.2

184.1

50.2

BASIC UNIT W/ ECON.

191.0

49.9

191.0

49.9

BASIC UNIT W/ ECON. & HEATING

187.4

50.0

187.4

50.0

BASIC UNIT W/ ECON. & HEATING & POWER

EXHAUST

194.9

49.5

194.9

49.5

MODEL

060

061

X

Y

X

Y

BASIC UNIT

179.8

49.9

179.6

50.0

BASIC UNIT W/ ECON.

186.7

49.7

186.5

49.7

BASIC UNIT W/ ECON. & HEATING

183.5

49.8

183.2

49.8

BASIC UNIT W/ ECON. & HEATING & POWER

EXHAUST

190.9

49.3

190.7

49.3

UNIT WEIGHTS

LD08298

Advertising