York ECO2 YPAL 050 User Manual

Page 147

Advertising
background image

147

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

7

TABLE 7-1 – DEFINITIONS (CONTINUED)

Continued on next page

MENU ITEM

DEFINITION

HSP1

THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 1 TO THE

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

HSP2

THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 2 TO THE

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

HSP3

THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 3 TO THE

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

HSP4

THIS IS THE STATUS OF THE BINARY INPUT FROM THE HIGH

PRESSURE SWITCH FOR COMPRESSOR SYSTEM 4 TO THE

UNIT CONTROLLER. ON - OKAY, OFF - FAULTED.

HYDRONIC HEAT ACTUATOR VALVE REVERSE

ACTING

THIS PARAMETER REVERSES THE ACTION OF THE HYDRONIC

VALVE. WHEN THE PARAMETER IS TURNED ON A 2 VOLT INPUT

TO THE VALVE IS FULL OPEN AND A 10 VOLT INPUT TO THE

VALVE IS FULL CLOSED

HYDRONIC HEATING ENABLED

THIS PARAMETER MUST BE TURNED ON TO ENABLE HYDRONIC

HEATING OPERATION

HYDRONIC HEATING STAGE #1 SUPPLY AIR

SETPOINT

THIS PARAMETER ESTABLISHES THE SETPOINT FOR

CONSTANT VOLUME HYDRONIC HEATING OPERATION DURING

FIRST STAGE OPERATION

HYDRONIC HEATING STAGE #2 SUPPLY AIR

SETPOINT

THIS PARAMETER ESTABLISHES THE SETPOINT FOR

CONSTANT VOLUME HYDRONIC HEATING OPERATION DURING

SECOND STAGE OPERATION AND ALSO THE CONTROL

SETPOINT FOR VAV HYDRONIC HEATING OPERATION

IAQ SENSOR RANGE

THIS PARAMETER IDENTIFIES TO THE UNIT CONTROLLER THE

RANGE OF THE CO2 SENSOR IN PPM

IAQ SETPOINT

THE UNIT CONTROLLER WILL TRY AND MAINTAIN THE CO2

LEVEL IN THE SPACE TO WITHIN +/- 100 PPM OF THIS VALUE

INDOOR FAN (G)

THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL G

- SUPPLY FAN

INDOOR FAN MIN RUN TIME

THIS GIVES THE STATUS OF THE MINIMUM SUPPLY FAN RUN

TIME IN SECONDS

INDOOR FAN OUTPUT

THIS GIVES THE STATUS OF THE BINARY OUTPUT FROM THE

UNIT CONTROLLER TO THE SUPPLY FAN

INDOOR FAN VFD OUTPUT

THIS GIVES THE STATUS OF THE ANALOG OUTPUT FROM THE

UNIT CONTROLLER TO THE SUPPLY FAN IN %

INPUT AIR PROVING SWITCH

THIS IS THE STATUS OF THE AIR PROVING SWITCH INPUT TO

THE UNIT CONTROLLER, OFF OR ON

INPUT DIRTY FILTER SWITCH

THIS IS THE STATUS OF THE DIRTY FILTER SWITCH INPUT TO

THE UNIT CONTROLLER, OFF - CLEAN FILTER, ON - DIRTY

FILTER

INPUT INDOOR FAN OVERLOAD SWITCH

THIS GIVES THE STATUS OF THE BINARY INPUT FROM THE

SUPPLY FAN OVERLOAD TO THE UNIT CONTROLLER, OFF -

FAULT, ON - NORMAL OPERATION