Installation

FIG. 2-8 – FIELD CONTROL WIRING CONNECTIONS

LD13002

Wiring Notes:
1. Wiring shown indicates typical wiring. Refer to the IOM manual for more detailed wiring methods and options.
2. All wiring is Class 2, low voltage.
3. Maximum power available from the 24 VAVC terminal is 40 VA.
4. Use shielded wire where shown.

FIELD CONTROL WIRING CONNECTIONS

Y4 (Cool Stage 4)

Y4

Y3 (Cool Stage 3)

Y3

Y2 (Cool Stage 2)

Y2

Y1 (Cool Stage 1)

Y1

W3 (Heating Stage 3)

W3

W2 (Heating Stage 2)

W2

W1 (Heating Stage 1)

W1

G (Fan)

G

R (24 VAC)

R

C (Common)

C

X

FAULT
LIGHT

(Optional)

10 WIRE THERMOSTAT

R

OCC

PURGE

BAS ECON +

BAS ECON -

Use shielded wire

BAS ECONOMIZER

INPUT

0-10 VDC

(Field Supplied)

VAV OPEN +

VAV OPEN -

VAV HEAT RELAY

24 VDC

RELAY

(Field Supplied)

CO2 SENSOR

(Field Supplied)

0-2000 PPM

0-10 VDC OUTPUT

Use Shielded

Wire

Use Shielded Wire

Use

Shielded

Wire

DV+

DV-

SUPPLY AIR

TEMP RESET

0-10 VDC

(Field Supplied)

REM +

ST

SD1

R

REM -

GND

SSO

SPACE

SENSOR

10K TYPE III

THERMISTOR

COM

TMP

SPACE SENSOR

RESET

20K ADJUST

POTENTIOMETER

COM SET

Shutdown