Comfort ventilation, The unit must have an economizer installed, The unit must be in the occupied mode – York ECO2 YPAL 050 User Manual

Page 81

Advertising
background image

81

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

5

COMFORT VENTILATION

Comfort Ventilation is a Constant Volume control
mode that uses the economizer to control the supply
air temperature. When outdoor air conditions allow,
the economizer will modulate the outside / return air
mix to keep supply air temperatures within the upper
and lower Comfort Ventilation set points. The control
will modulate the economizer, and energize cooling or
heating if necessary, to keep the supply air temperature
within the Comfort Ventilation set points, even though
the space temperature requirements are satisfi ed.

The following criteria must be present in order for
Comfort Ventilation to function”:

The unit can not be in an active heating or cooling

mode.

The unit must have an economizer installed.

The unit must be in the occupied mode.

The unit should be placed in the continuous in-

door fan operation mode.

The unit type must be Constant Volume.

The following parameters must be programmed:

“COMFORT VENTILATION FOR COOLING
ENABLED”
- must be enabled under the COOLING
SETUP tab in the Simplicity PC software package.

“COMFORT VENTILATION FOR HEATING
ENABLED”
- must be enabled under the HEATING
SETUP tab in the Simplicity PC software package.

“COMFORT VENTILATION UPPER SETPOINT” -
must be programmed under the COOLING SETUP or
HEATING SETUP tab in the Simplicity PC software
package.

“COMFORT VENTILATION LOWER SETPOINT” -
must be programmed under the COOLING SETUP or
HEATING SETUP tab in the Simplicity PC software
package.

TABLE 5-4 OPERATION DURING OFF CYCLE

OAT VS OAT COMFORT ZONE

SAT VS SAT COMFORT ZONE

ECON OPERATION

HEAT STAGE

COMP STAGE

BELOW

ABOVE

OPEN

-

-

BELOW

BELOW

-

TURN ON

BELOW

WITHIN

-

-

-

ABOVE

ABOVE

-

-

TURN ON

ABOVE

BELOW

OPEN

-

-

ABOVE WITHIN

-

-

-

WITHIN

ABOVE

OPEN

-

-

WITHIN

BELOW

OPEN

-

-

WITHIN

WITHIN

-

-

-

TABLE 5-5 COMPRESSOR ON WHEN SPACE INPUT SATISFIED

OAT VS OAT COMFORT ZONE

SAT VS SAT COMFORT ZONE

ECON OPERATION

HEAT STAGE

COMP STAGE

BELOW

ABOVE

OPEN

-

TURN OFF

BELOW

BELOW

-

TURN ON

TURN OFF

BELOW

WITHIN

-

-

TURN OFF

ABOVE

ABOVE

-

-

LEAVE ON

ABOVE

BELOW

OPEN

-

LEAVE ON*

ABOVE WITHIN

-

-

LEAVE

ON

WITHIN

ABOVE

OPEN

-

TURN OFF

WITHIN

BELOW

OPEN

-

TURN OFF

WITHIN

WITHIN

-

-

TURN OFF

* If the economizer damper opens to 100%, the compressor will turn off and the economizer damper will remain
at 100%.