Occupied heating, Unoccupied heating, Space sensor – hard wired or communicated – York ECO2 YPAL 050 User Manual

Page 65: Cooling operation – occupied or unoccupied

Advertising
background image

65

JOHNSON CONTROLS

FORM 100.50-NOM6 (1207)

5

Occupied Heating

There are three stages of heating available:

W1 – First Stage of Heating

W2 – Second Stage of Heating

W3 – Third Stage of Heating

See the Heating section of this manual for a description
of the heating staging.

Unoccupied Heating

Unoccupied heating operation is the same as Occupied.
A programmable thermostat would be required in order
to change the heating temperature settings between
occupied and unoccupied.

Space Sensor – Hard Wired or Communicated

The following System Parameters must be programmed
through the Simplicity Control:

“CV OCCUPIED COOLING SETPOINT” – us-

ing Parameter 10 under the PROGRAM key on
the Simplicity control board or under the COOL-
ING SETUP tab in the Simplicity PC software
package.

“CV OCCUPIED HEATING SETPOINT” – us-

ing Parameter 11 under the PROGRAM key on
the Simplicity control board or under the HEAT-
ING SETUP tab in the Simplicity PC software
package.

“CV UNOCCUPIED COOLING SETPOINT”

– using Parameter 12 under the PROGRAM
key on the Simplicity control board or under
the COOLING SETUP tab in the Simplicity PC
software package.

“CV UNOCCUPIED HEATING SETPOINT”

– using Parameter 13 under the PROGRAM
key on the Simplicity control board or under
the HEATING SETUP tab in the Simplicity PC
software package.

Cooling Operation – Occupied or Unoccupied

The Simplicity Control will stage on the cooling as
follows:

At cooling start up

– If the space temperature is between 1.5° F and

1.9° F above the “CV OCCUPIED COOLING
SETPOINT”
or “CV UNOCCUPIED COOL-
ING SETPOINT”
the control will turn on the
fi rst compressor from System 1 and turn on a
5 minute timer.

– If after 5 minutes the space temperature is

between 1.5° F and 1.9° F above the “CV
OCCUPIED COOLING SETPOINT”
or “CV
UNOCCUPIED COOLING SETPOINT”
the
control will bring on the second compressor
of System 1 and start a 5-minute timer.

OR

– If the space temperature is greater than 2.0° F

or more above the “CV OCCUPIED COOL-
ING SETPOINT”
or “CV UNOCCUPIED
COOLING SETPOINT”
the control will bring
on the fi rst compressor from System 1 and
start a 3 minute timer. After 30 seconds, the
control will bring on the second compressor
from System 1.

If after 3 or 5 minutes the space temperature is

between 1.5° F and 1.9° F above the “CV OC-
CUPIED COOLING SETPOINT”
or “CV UN-
OCCUPIED COOLING SETPOINT”
the control
will bring on the fi rst compressor from System 2
and start a 5 minute timer.

If after 3 or 5 minutes the space temperature

is 2.0° F or more above the “CV OCCUPIED
COOLING SETPOINT”
or “CV UNOCCUPIED
COOLING SETPOINT”
the control will bring
on the fi rst compressor of System 2 and start a 3
minute timer.

If after 3 or 5 minutes the space temperature

is 1.5° F or more above the “CV OCCUPIED
COOLING SETPOINT”
or “CV UNOCCUPIED
COOLING SETPOINT”
the control will bring on
the second compressor of System 2.