York ZJ R-410A User Manual

Page 46

Advertising
background image

251934-YTG-G-0708

46

Johnson Controls Unitary Products

115°F

125°F

5000

77

259.6

28.3

108.9

88.3

67.7

-

-

-

239.1

30.7

99.0

81.5

61.1

-

-

-

72

242.3

27.7

146.8 126.2 105.6

85.0

-

-

224.6

30.0

140.1 119.7

99.2

78.8

-

-

67

225.0

27.1

184.8 164.2 143.6 122.9 102.3

-

210.0

29.3

178.3 157.8 137.4 116.9

96.5

-

62

207.6

26.7

207.6 207.2 174.1 153.5 132.9 112.3

193.3

28.9

193.3 193.3 165.0 144.6 124.1 103.7

6000

77

267.9

28.3

120.8

97.4

74.1

-

-

-

246.8

30.6

113.8

90.5

67.2

-

-

-

72

250.0

27.7

162.3 139.0 115.6

92.3

-

-

231.8

29.9

155.7 132.4 109.2

85.9

-

-

67

232.2

27.1

203.9 180.5 157.2 133.8 110.5

-

216.8

29.2

197.6 174.4 151.1 127.8 104.6

-

62

214.3

26.6

214.3 214.0 190.6 167.3 143.9 120.6

199.5

28.8

199.5 199.5 181.6 158.3 135.0 111.7

57

215.4

26.7

215.4 215.1 191.8 168.4 145.1 121.7

203.0

29.0

203.0 202.7 179.0 155.7 132.4 109.1

7000

77

276.2

28.2

132.7 106.6

80.5

-

-

-

254.5

30.5

128.5

99.4

73.4

-

-

-

72

257.8

27.6

177.9 151.8 125.7

99.6

-

-

239.0

29.8

171.3 145.2 119.1

93.0

-

-

67

239.4

27.0

223.0 196.9 170.8 144.7 118.6

-

223.5

29.1

217.0 190.9 164.8 138.7 112.7

-

62

220.9

26.6

220.9 220.8 207.2 181.1 155.0 128.9

205.7

28.7

205.7 205.7 198.1 172.0 145.9 119.8

57

222.0

26.7

222.0 221.9 208.4 182.3 156.2 130.1

209.3

28.9

209.3 209.2 195.3 169.2 143.1 117.0

8000

77

284.5

28.2

144.7 115.8

86.9

-

-

-

262.2

30.4

143.3 108.4

79.5

-

-

-

72

265.6

27.6

193.4 164.6 135.7 106.9

-

-

246.3

29.7

186.8 157.9 129.0 100.1

-

-

67

246.6

27.0

242.2 213.3 184.5 155.6 126.8

-

230.3

29.1

230.3 207.4 178.5 149.7 120.8

-

62

227.6

26.5

227.6 227.6 223.7 194.9 166.0 137.2

212.0

28.6

212.0 212.0 212.0 185.7 156.8 127.9

57

228.7

26.6

228.7 228.7 225.1 196.2 167.4 138.5

215.7

28.8

215.7 215.7 211.6 182.7 153.8 124.9

9000

72

264.8

27.7

204.0 172.5 141.1 109.6

-

-

244.6

29.8

195.9 164.7 133.5 102.2

-

-

67

245.9

27.1

243.6 223.2 191.7 160.3 128.8

-

228.7

29.1

228.7 216.0 184.7 153.5 122.2

-

62

226.9

26.6

226.9 226.9 225.0 193.5 162.0 130.5

210.5

28.7

210.5 210.5 210.5 180.6 149.3 118.1

57

228.0

26.7

228.0 228.0 226.2 194.7 163.2 131.8

214.2

28.9

214.2 214.2 212.2 180.9 149.7 118.5

10000

72

263.9

27.8

214.6 180.5 146.4 112.3

-

-

242.9

29.9

205.1 171.5 137.9 104.3

-

-

67

245.1

27.2

245.1 233.1 199.0 164.9 130.8

-

227.2

29.2

227.2 224.5 190.9 157.3 123.7

-

62

226.2

26.7

226.2 226.2 226.2 192.1 158.0 123.9

209.1

28.8

209.1 209.1 209.1 175.5 141.9 108.3

57

227.3

26.8

227.3 227.3 227.3 193.2 159.1 125.0

212.8

29.0

212.8 212.8 212.8 179.2 145.6 112.0

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower

Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZF240 (20 Ton) (Continued)

Air on

Evaporator Coil

Temperature of Air on Condenser Coil

Total

Capacity

1

(MBh)

Total
Input

(kW)

2

Sensible Capacity (MBh)

Total

Capacity

1

(MBh)

Total
Input

(kW)

2

Sensible Capacity (MBh)

CFM

WB
(°F)

Return Dry Bulb (°F)

Return Dry Bulb (°F)

90

85

80

75

70

65

90

85

80

75

70

65

Advertising