York ZJ R-410A User Manual

Page 67

Advertising
background image

251934-YTG-G-0708

Johnson Controls Unitary Products

67

Altitude/Temperature Correction Factors

Air

Temp.

Altitude (Ft.)

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

40

1.060

1.022

0.986

0.950

0.916

0.882

0.849

0.818

0.788

0.758

0.729

50

1.039

1.002

0.966

0.931

0.898

0.864

0.832

0.802

0.772

0.743

0.715

60

1.019

0.982

0.948

0.913

0.880

0.848

0.816

0.787

0.757

0.729

0.701

70

1.000

0.964

0.930

0.896

0.864

0.832

0.801

0.772

0.743

0.715

0.688

80

0.982

0.947

0.913

0.880

0.848

0.817

0.787

0.758

0.730

0.702

0.676

90

0.964

0.929

0.897

0.864

0.833

0.802

0.772

0.744

0.716

0.689

0.663

100

0.946

0.912

0.880

0.848

0.817

0.787

0.758

0.730

0.703

0.676

0.651

Gas Heat Minimum Supply Air

Size

(Tons)

Heat Size

Supply Air (CFM)

Cooling

Heating

Min

Max

Min

Max

180

(15)

24 4500

7000

4500

7000

32

4500

7000

4500

7000

210

(17.5)

24 6000

8750

6000

8750

32

6000

8750

6000

8750

240

(20)

24 6000

9400

6000

9400

32

6000

9400

6000

9400

300

(25)

24 7500

12500

7500

12500

32

7500

12500

7500

12500

0.600

0.650

0.700

0.750

0.800

0.850

0.900

0.950

1.000

1.050

1.100

40

50

60

70

80

90

100

Air Temperature (ºF)

Correction Factor

Sea Level

1000 ft

2000 ft

3000 ft

4000 ft

6000 ft

7000 ft

8000 ft

9000 ft

10000 ft

5000 ft

For units with VFD and gas heat, the speed of the indoor
blower motor continues to be controlled by duct static
pressure via the VAV control board.

If there are VAV boxes present in the duct system,

the boxes must be driven to the full-open position

using a customer-supplied power source to assure

adequate airflow across electric heating elements

or gas heat exchanger tubes.

Advertising