Advertising
background image

251934-YTG-G-0708

Johnson Controls Unitary Products

75

300

(25)

208-3-60 23.0

160

31.5

3.7

38.6

0.0

None

-

-

-

155.1

175

E18

13.5

1

37.5

155.1

175

E36

27.0

2

74.9

155.1

175

E54

40.6

2

112.7

189.1

200

E72

54.1

2

150.2

198.4

225

230-3-60 23.0

160

31.5

3.7

38.6

0.0

None

-

-

-

155.1

175

E18

18.0

1

43.3

155.1

175

E36

36.0

2

86.6

156.5

175

E54

54.0

2

129.9

178.2

200

E72

72.0

2

173.2

221.5

250

460-3-60 12.2

87

17.1

1.9

19.3

0.0

None

-

-

-

80.5

90

E18

18.0

1

21.7

80.5

90

E36

36.0

2

43.3

80.5

90

E54

54.0

2

65.0

89.1

100

E72

72.0

2

86.6

110.7

125

575-3-60 8.7

62

13.5

1.5

15.4

0.0

None

-

-

-

60.1

70

E18

18.0

1

17.3

60.1

70

E36

36.0

2

34.6

62.6

70

E54

54.0

2

52.0

71.2

80

E72

72.0

2

69.3

88.5

100

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

ZJ180-300 - High Static Drive Without Powered Convenience Outlet (Continued)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max Fuse

2

/

Breaker

3

Size

(Amps)

RLA LRA MCC

FLA

FLA

FLA

Model

kW

Stages

Amps

Advertising