York ZJ R-410A User Manual

Page 51

Advertising
background image

251934-YTG-G-0708

Johnson Controls Unitary Products

51

ZJ300 (25 Ton) Side Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Low Static 7.5 HP &
Field Supplied Drive

Low Static 7.5 HP & Drive

6600

760 2.51 793 3.11 824 3.68 856 4.23 887 4.74 919 5.23 950 5.70 983 6.15

7000

775 2.99 808 3.60 839 4.17 871 4.71 902 5.22 934 5.72 966 6.19 998 6.64

7400

792 3.51 824 4.11 856 4.69 887 5.23 918 5.74 950 6.24 982 6.70 1014 7.16

S

ta

nda
rd 10 HP

&

Dr

ive

7800

809 4.07 841 4.67 873 5.24 904 5.78 935 6.30 967 6.79 999 7.26 1031 7.71

8200

826 4.66 859 5.27 890 5.84 922 6.38 953 6.89 985 7.39 1016 7.86 1049 8.31

8600

845 5.30 877 5.90 909 6.47 940 7.01 972 7.53 1003 8.02 1035 8.49 1067 8.94

9000

864 5.97 896 6.57 928 7.14 960 7.69 991 8.20 1022 8.69 1054 9.16 1087 9.61

9400

884 6.68 916 7.28 948 7.86 980 8.40 1011 8.91 1042 9.41 1074 9.88 1107 10.33

9800

905 7.43 937 8.04 969 8.61 1000 9.15 1032 9.67 1063 10.16 1095 10.63 1127 11.08

10200

926 8.22 958 8.83 990 9.40 1021 9.94 1053 10.46 1084 10.95 1116 11.42 1148 11.87

10600

948 9.05 980 9.66 1012 10.23 1043 10.77 1075 11.29 1106 11.78 1138 12.25 1170 12.70

11000

970 9.92 1003 10.52 1034 11.09 1066 11.64 1097 12.15 1128 12.64 1160 13.11 1193 13.56

11400

993 10.82 1025 11.43 1057 12.00 1089 12.54 1120 13.06 1151 13.55 1183 14.02 1216 14.47

11800

1017 11.76 1049 12.37 1081 12.94 1112 13.48 1143 14.00 1175 14.49 1207 14.96 1239 15.41

12200

1040 12.74 1073 13.34 1104 13.91 1136 14.46 1167 14.97 1199 15.46 1231 15.93 1263 16.38

12600

1065 13.75 1097 14.35 1129 14.92 1160 15.47 1192 15.98 1223 16.47 1255 16.94

-

-

High Static 15 HP & Drive

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC

RESISTANCE table for additional applications.

2. See RPM SELECTION table to determine desired motor sheave setting and to

determine the maximum continuous BHP.

3. kW = BHP x 0.82.

2.0

2.2

2.4

2.6

2.8

3.0

3.2

3.4

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard 10 HP & Drive

High Static 15 HP & Drive

6600

1016 6.59 1050 7.00 1086 7.41 1123 7.81 1161 8.19 1202 8.58 1244 8.95 1289 9.33

7000

1031 7.07 1065 7.49 1101 7.89 1138 8.29 1176 8.68 1217 9.06 1259 9.44 1304 9.82

7400

1047 7.59 1081 8.01 1117 8.41 1154 8.81 1192 9.20 1233 9.58 1275 9.96 1320 10.34

7800

1064 8.14 1098 8.56 1134 8.97 1171 9.36 1209 9.75 1250 10.13 1292 10.51 1337 10.89

8200

1082 8.74 1116 9.16 1152 9.56 1189 9.96 1227 10.35 1268 10.73 1310 11.11 1355 11.49

8600

1101 9.37 1135 9.79 1170 10.20 1207 10.59 1246 10.98 1286 11.36 1329 11.74 1374 12.12

9000

1120 10.05 1154 10.46 1189 10.87 1226 11.27 1265 11.65 1305 12.04 1348 12.41 1393 12.79

9400

1140 10.76 1174 11.18 1209 11.58 1246 11.98 1285 12.37 1325 12.75 1368 13.13 1413 13.51

9800

1160 11.51 1195 11.93 1230 12.33 1267 12.73 1306 13.12 1346 13.50 1389 13.88 1434 14.26

10200

1182 12.30 1216 12.72 1251 13.12 1288 13.52 1327 13.91 1367 14.29 1410 14.67 1455 15.05

10600

1204 13.13 1238 13.55 1273 13.95 1310 14.35 1349 14.74 1389 15.12 1432 15.50 1477 15.88

11000

1226 14.00 1260 14.41 1296 14.82 1332 15.22 1371 15.60 1412 15.99 1454 16.36 1499 16.74

11400

1249 14.90 1283 15.32 1318 15.72 1355 16.12 1394 16.51 1434 16.89

-

-

-

-

11800

1272 15.84 1306 16.26 1342 16.66 1379 17.06

-

-

-

-

-

-

-

-

12200

1296 16.82 1330 17.23

-

-

-

-

-

-

-

-

-

-

-

-

12600

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

15 HP & Field Supplied Drive

Advertising