York ZJ R-410A User Manual

Page 66

Advertising
background image

251934-YTG-G-0708

66

Johnson Controls Unitary Products

Drive Selection

1.

Determine desired airflow.

2.

Calculate or measure the amount of external static pressure.

3.

Using the operating point determined from steps 1 & 2, locate this point on the appropriate supply air blower performance table.
(Linear interpolation may be necessary.)

4.

Noting the RPM and BHP from step 3, locate the appropriate model and drive on the RPM selection table.

5.

Review the BHP compared to the motor options available. Select the appropriate motor.

6.

Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.

7.

Determine turns open to obtain the desired operation point.

Example

1.

19000 CFM

2.

5.4 iwg

3.

Using the supply air blower performance table below, the following data point was located: 1150 RPM & 36 BHP.

4.

Using the RPM selection table below, Size X and Model Y is found.

5.

36 BHP exceeds the maximum continuous BHP rating of the 30 HP motor. The 40 HP motor is required.

6.

1150 RPM is within the range of the 30 & 40 HP drives, but step 5 requires the 40 HP motor.

7.

Using the 40 HP motor and drive, 5.5 turns open will achieve 1150 RPM.

Example Supply Air Blower Performance

Air Flow

(CFM)

Available External Static Pressure - IWG

3.0

3.4

3.8

4.2

4.6

5.0

5.4

5.8

6.2

6.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

30 HP & Field Supplied Drive

Standard 30 HP & Drive

Alternate 40 HP & Drive

18000

800

10.00

850

14.00

900

18.00

950

22.00 1000 26.00 1050 30.00 1100

34.00 1150

38.00 1200

42.00

1250

46.00

19000

850

12.00

900

16.00

950

20.00

1000 24.00 1050 28.00 1100 32.00 1150

36.00 1200

40.00 1250

44.00

1300

48.00

20000

900

14.00

950

18.00

1000 22.00

1050 26.00 1100 30.00 1150 34.00 1200

38.00 1250

42.00 1300

46.00

1350

50.00

21000

950

16.00

1000

20.00

1050 24.00

1100 28.00 1150 32.00 1200 36.00 1250

40.00 1300

44.00 1350

48.00

1400

52.00

Table X: RPM Selection

Size

(Tons)

Model

HP

Max

BHP

Motor

Sheave

Blower

Sheave

6 Turns

Open

5 Turns

Open

4 Turns

Open

3 Turns

Open

2 Turns

Open

1 Turn

Open

Fully

Closed

X

Y

30

34.50

1VL51

BK99

1000

1025

1045

1060

1110

1150

N/A

40

46.00

1VL63

BK67

1125

1175

1250

1325

1400

1475

N/A

Advertising