Airflow Performance

ZJ180-300 Side Duct Application

ZJ180 (15 Ton) Side Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.898.

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard 5 HP & Field Supplied Drive

Standard 5 HP & Drive

High Static 5 HP & Drive

4000

727 1.14 765 1.47 806 1.77 848 2.04 891 2.29 934 2.52 977 2.73 1020 2.93 1061 3.12 1101 3.30 1138 3.48 1174 3.67

4400

753 1.51 792 1.84 832 2.14 874 2.41 917 2.66 960 2.88 1004 3.09 1046 3.29 1087 3.48 1127 3.67 1165 3.85 1200 4.03

4800

781 1.92 820 2.25 861 2.55 903 2.82 946 3.06 989 3.29 1032 3.50 1074 3.70 1116 3.89 1155 4.08 1193 4.26 1228 4.44

5200

812 2.37 850 2.70 891 3.00 933 3.27 976 3.52 1019 3.74 1062 3.95 1105 4.15 1146 4.34 1186 4.53 1223 4.71 1259 4.89

5600

844 2.86 882 3.19 923 3.49 965 3.76 1008 4.01 1051 4.23 1094 4.45 1137 4.64 1178 4.83 1218 5.02 1255 5.20 1291 5.39

6000

877 3.39 916 3.72 957 4.02 999 4.29 1042 4.54 1085 4.76 1128 4.98 1170 5.17 1212 5.36 1251 5.55 1289 5.73

-

-

6400

912 3.96 951 4.29 992 4.59 1034 4.86 1077 5.10 1120 5.33 1163 5.54 1205 5.74

-

-

-

-

-

-

-

-

6800

949 4.56 988 4.89 1028 5.19 1070 5.46 1113 5.71

-

-

-

-

-

-

-

-

-

-

-

-

-

-

7200

986 5.20 1025 5.53

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

5 HP & Field Supplied Drive

ZJ210 (17.5 Ton) Side Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard 5 HP & Field Supplied Drive

Standard 5 HP & Drive

High Static 7.5 HP & Drive

4400

636 0.65 672 1.14 709 1.60 745 2.03 780 2.43 815 2.78 849 3.09 882 3.35 914 3.55 944 3.70 973 3.78 999 3.79

4800

649 0.99 685 1.48 721 1.94 757 2.37 793 2.77 828 3.12 862 3.43 895 3.69 927 3.89 957 4.04 985 4.12 1012 4.13

5200

663 1.34 700 1.83 736 2.29 772 2.72 808 3.11 843 3.47 877 3.78 910 4.04 942 4.24 972 4.39 1000 4.47 1027 4.48

5600

680 1.71 717 2.20 753 2.66 789 3.09 825 3.48 860 3.84 894 4.15 927 4.41 959 4.61 989 4.76 1017 4.84 1044 4.85

6000

699 2.11 735 2.60 772 3.06 808 3.49 844 3.88 879 4.24 913 4.55 946 4.80 977 5.01 1007 5.15 1036 5.24 1062 5.25

6400

719 2.55 756 3.03 792 3.49 828 3.92 864 4.32 899 4.67 933 4.98 966 5.24 998 5.45 1028 5.59 1056 5.67 1083 5.68

6800

742 3.02 778 3.51 814 3.97 850 4.40 886 4.79 921 5.15 955 5.46 988 5.72 1020 5.92 1050 6.07 1078 6.15 1105 6.16

7200

765 3.54 802 4.03 838 4.49 874 4.92 910 5.32 945 5.67 979 5.98 1012 6.24 1044 6.44 1074 6.59 1102 6.67 1129 6.68

7600

790 4.11 827 4.60 863 5.06 899 5.49 935 5.88 970 6.24 1004 6.55 1037 6.81 1069 7.01 1099 7.16 1127 7.24 1154 7.25

8000

817 4.72 853 5.21 890 5.67 926 6.10 962 6.50 997 6.85 1031 7.16 1064 7.42 1095 7.62 1125 7.77 1154 7.85 1180 7.86

8400

845 5.38 881 5.87 918 6.33 954 6.76 990 7.16 1025 7.51 1059 7.82 1092 8.08 1123 8.28 1153 8.43 1182 8.51 1208 8.52

8800

874 6.09 911 6.58 947 7.04 983 7.47 1019 7.86 1054 8.22 1088 8.53

-

-

-

-

-

-

-

-

-

-

7.5 HP & Field Supplied Drive