Status Registers
Overview

76

Operating Manual for Multichannel Functionality (GPIB-M)

Table 4.7 QUEStionable Status Register

VOLTage

Sub-Register

This shows whether the present voltage level is over or under the specified trip limit.

Table 4.8 VOLTage Sub-Register

Bit

Bit Weight

Bit Name

Description

0

1

VOLTage Summary

Reflects a summary of the
VOLTage Sub-Register.

1

2

CURRent Summary

Reflects a summary of the
CURRent Sub-Register.

2

4

TIME Not

implemented

3

8

Reserved

4

16

Over Temperature

Indicates the OTP circuit has
tripped.

5

32

FREQuency Summary

Not implemented

6

64

PHASe Summary

Not implemented

7

128

MODulation Summary

Not implemented

8

256

CALibration

Indicates an error in the unit
calibration.

9

512

Not Used

Not implemented

10

1024

Not Used

Not implemented

11

2048

AC Off

Indicates an AC Supply failure.

12

4096

UNRegulated

Indicates that the output is not
regulated in either Constant
Voltage mode, Constant Current
mode or Constant Power mode.
Reflects the inverse of the
Operation Regulation Summary bit.

13

8192

INSTrument Summary

Not implemented

14

16384

Command Warning

Not implemented

15

32768

Not Used

Always zero

Bit

Bit Weight

Bit Name

Description

0

1

Over VOLtage

Set if the supply’s output voltage
exceeds the over-voltage trip level,
either user-specified variable trip limit,
or the fixed trip limit.

1

2

Under VOLtage

Set if the supply’s output voltage is less
than the user-specified under-voltage
trip level (variable trip limit) and the
supply is in Operation state.