Unitary Products Group

All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.

Physical and Electrical Data

-

1 Phase

MODEL

EABD-F018S EABD-F024S EABD-F030S EABD-F036S EABD-F042S EABD-F048S EABD-F060S

Unit Supply Voltage

208-230V, 1

φ, 60Hz

Normal Voltage Range

1

187 to 252

Minimum Circuit Ampacity

9.9

15.0

16.9

19.8

25.0

32.7

37.8

Max. Overcurrent Device Amps

2

15

25

25

30

40

50

60

Min. Overcurrent Device Amps

3

15

20

20

20

30

35

40

Compressor Type

4

Recip

Recip

Recip

Recip

Recip

Scroll

D

Scroll

D

Compressor
Amps

Rated Load

7.5

10.7

12.4

14.6

18.8

25.0

29.1

Locked Rotor

41

44

60

78

78

115

150

Crankcase Heater

Yes

Yes

Yes

Yes

Yes

No

No

Fan Motor Amps Rated Load

0.5

1.5

1.5

1.5

1.5

1.5

1.5

Fan Diameter Inches

22

22

22

22

22

24

24

Fan Motor

Rated HP

1/15

1/4

1/4

1/4

1/4

1/4

1/4

Nominal RPM

850

850

850

850

850

850

850

Nominal CFM

2,000

3,250

3,450

3,500

3,500

3,400

3,500

Coil

Face Area Sq. Ft.

15.72

18.34

20.96

23.58

23.58

24.00

27.00

Rows Deep

1

1

1

1

1

2

2

Fin / Inches

22

22

22

22

22

18

18

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

7/8

7/8

7/8

7/8

1-1/8

Unit Charge (Lbs. - Oz.)

5

7 - 1

6 - 6

8 - 7

8 - 7

8 - 7

12 - 8

16 - 7

Charge Per Foot, Oz.

0.68

0.68

0.70

0.70

0.70

0.70

0.76

Operating Weight Lbs.

172

184

196

208

208

250

294

1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
5. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15

feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

A

B

C

Unit

Model

Dimensions

(Inches)

Refrigerant

Connection

Service Valve Size

A

1

1. Including Fan Guard.
* Adapter fitting required for 1-1/8” line set.

B

C

Liquid

Vapor

018

27

37

27

3/8”

3/4”

024

31

37

27

030

35

37

27

7/8”

036

39

37

27

042

39

37

27

048

34

43

32

060

38

43

32

7/8”*