Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature

*

= Single-phase outdoor units only.

*

= Single-phase outdoor units only.

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

EABD-F048S, EABD-(T,W)048S**

INDOOR COIL MODEL NO.

FC/MC/PC/UC60

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

1400

1600

1800

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

43.2

47.1

45.4

49.6

51.0

46.2

48.0

45.8

49.7

51.3

49.2

48.8

46.2

49.7

51.6

S.C.

42.7

41.7

34.8

34.3

26.0

43.8

43.3

37.1

36.6

27.7

44.8

44.8

39.4

38.8

29.5

K.W.

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

2.4

75

T.C.

43.1

45.5

43.5

47.8

49.9

45.7

46.6

44.0

48.2

50.2

48.3

47.7

44.5

48.6

50.5

S.C.

41.4

40.6

33.9

33.7

25.8

42.6

42.2

36.2

36.0

27.4

43.8

43.7

38.5

38.2

29.0

K.W.

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

2.7

85

T.C.

42.9

43.8

41.6

46.1

48.9

45.2

45.2

42.2

46.8

49.1

47.4

46.5

42.8

47.4

49.3

S.C.

40.1

39.5

33.1

33.1

25.6

41.5

41.0

35.3

35.4

27.1

42.8

42.6

37.5

37.7

28.6

K.W.

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

3.0

95

T.C.

42.8

42.1

39.7

44.3

47.9

44.7

43.8

40.4

46.0

48.0

46.5

45.4

41.1

46.3

48.2

S.C.

38.9

38.4

32.2

32.5

25.4

40.4

39.9

34.4

35.4

26.8

41.9

41.4

36.6

37.2

28.1

K.W.

3.3

3.3

3.3

3.3

3.3

3.3

3.3

3.3

3.4

3.4

3.3

3.3

3.3

3.3

3.3

105

T.C.

40.5

40.2

37.6

42.1

45.0

42.6

41.8

38.2

42.9

45.4

44.7

43.4

38.8

43.7

45.7

S.C.

37.1

36.7

31.2

31.7

24.5

38.5

38.2

33.2

34.0

25.9

40.0

39.6

35.2

36.3

27.3

K.W.

3.7

3.7

3.7

3.7

3.7

3.7

3.7

3.7

3.7

3.7

3.7

3.7

3.7

3.7

3.7

115

T.C.

38.2

38.3

35.5

40.0

42.2

40.6

39.9

36.0

40.6

42.8

43.0

41.4

36.6

41.2

43.3

S.C.

35.4

35.1

30.3

30.9

23.5

36.8

36.5

32.1

33.2

25.0

38.1

37.8

33.9

35.5

26.5

K.W.

4.1

4.1

4.1

4.1

4.1

4.2

4.1

4.1

4.1

4.1

4.2

4.1

4.1

4.1

4.1

125

T.C.

35.9

36.5

33.4

37.9

39.4

38.6

37.9

33.9

38.3

40.2

41.3

39.4

34.4

38.8

40.9

S.C.

33.7

33.5

29.4

30.2

22.6

35.0

34.8

31.0

32.4

24.1

36.3

36.1

32.6

34.7

25.7

K.W.

4.6

4.5

4.5

4.5

4.5

4.6

4.5

4.5

4.5

4.6

4.6

4.5

4.5

4.5

4.6

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
**

For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.

Air Handler

Coil

T.C.

S.C.

KW

MA16C

FC60C

1.00

1.00

1.00

MA20D

FC/MC60D

1.00

1.00

1.00

MA20D

MC61D

1.00

1.00

1.00

AHP/SHP48

1.00

1.00

1.00

AHP/SHP60

1.00

0.98

1.00

F*FV060*

1.00

0.98

0.92

MV20D*

FC/MC60D

1.00

0.98

1.00

MV20D*

MC61D

1.01

0.98

1.01

AV/SV48*

1.01

0.98

1.01

HC60

0.99

0.97

0.99

HD60

0.98

0.98

0.98

MC61

1.00

1.00

1.00

Variable Speed
Furnace *

Coil

T.C.

S.C.

KW

FL9(C,V)D20

FC/MC/PC60D

1.00

1.00

1.00

(F,L)L8VC16

FC/PC60C

0.99

0.99

0.99

(F,L)L8VC20

FC/PC60C

1.00

1.00

1.00

FL9(C,V)C16

FC/PC60C

1.00

1.00

1.00

FL9(C,V)C20

FC/PC60C

1.00

0.97

1.00

FL9(C,V)D20

HC60

1.00

1.00

1.00

(F,L)L8VC20

HD60

1.00

1.00

1.00

FL9(C,V)C20

HD60

1.00

0.98

1.00

FL9(C,V)D20

MC61D

1.01

0.99

1.01

Advertising