PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-con-

necting line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for

evaporator + adder for line set.

Additional R-22 Charge / Orifice Size for Various Matched Systems - 3 Phase

Outdoor Unit

EABD-(T,W)030S

EABD-(T,W)036S

EABD-(T,W)042S

EABD-(T,W)048S

EABD-(T,W)060S

Required TXV

1TVM2A1

1TVM2A1

1TVM2C1

1TVM2C1

1TVM2C1

Factory Charge, lbs-oz

8 - 9

8 - 7

8 - 7

12 - 8

16 - 9

Indoor Coil

1

Additional Charge, Oz

FC/MC/PC/UC35B2C

0

9

FC/MC/PC/UC35C2C

0

9

FC/MC/PC/UC42B2C

0

9

FC/MC/PC/UC42C2C

0

9

FC/MC/PC/UC48C2C

9

14

FC/MC/PC/UC48D2C

9

14

FC/PC/UC60C2C

7

5

FC/MC/PC/UC60D2C

7

5

MC61D2C

7

5

HC36B2A

0

HC42C2C

9

HC60C2C

7

5

HD36B2A

0

9

HD48C2C

14

HD60D2C

7

5

AHP30B2A

0

AHP36C2A

9

AHP42C2C

9

AHP/SHP48D2C

14

7

AHP/SHP60D2C

7

5

FC/MC/PC/UC42B3X

0

9

FC/MC/PC/UC42X3X

0

9

FC/MC/PC/UC48C3X

9

14

FC/MC/PC/UC48D3X

9

14

FC/PC/UC60C3X

7

5

FC/MC/PC/UC60D3X

7

5

MC61D3X

7

5

HC36B3X

0

HC42C3X

9

HC60C3X

7

5

HD36B3X

0

9

HD48C3X

14

HD60D3X

7

5

AHP30B3X

0

AHP36C3X

9

AHP42C3X

9

AHP/SHP48D3X

14

7

AHP/SHP60D3X

7

5

F*FP040H06T2A

0

9

F*FP042H06T2A

9

FOOTNOTES:

1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.