246819-BTG-H-0208

20

Unitary Products Group

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

*

= Single-phase outdoor units only.

*

= Single-phase outdoor units only.

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

EABD-F030S, EABD-(T,W)030S**

INDOOR COIL MODEL NO.

FC/MC/PC35

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

800

1000

1200

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

28.5

31.9

31.9

34.8

34.4

30.7

32.7

34.5

34.2

33.7

32.9

33.5

37.2

33.6

33.9

S.C.

28.4

26.0

22.0

21.8

16.6

30.6

27.9

25.7

21.2

16.9

32.9

29.8

29.3

20.7

17.3

K.W.

1.8

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

75

T.C.

27.0

29.7

29.6

32.7

33.8

29.1

30.6

31.6

32.6

33.4

31.2

31.5

33.6

32.4

33.0

S.C.

26.9

25.1

21.2

21.1

16.5

29.0

27.2

24.4

21.6

17.2

31.1

29.4

27.5

22.1

17.9

K.W.

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.1

2.0

2.0

2.0

2.0

2.1

85

T.C.

25.4

27.6

27.2

30.7

33.2

27.4

28.5

28.6

31.0

33.2

29.4

29.5

30.0

31.2

33.1

S.C.

25.4

24.1

20.4

20.4

16.5

27.4

26.6

23.1

22.0

17.5

29.4

29.0

25.8

23.6

18.5

K.W.

2.1

2.2

2.2

2.2

2.2

2.2

2.2

2.2

2.2

2.3

2.2

2.2

2.2

2.2

2.3

95

T.C.

23.9

25.5

24.8

28.6

32.6

25.8

26.5

25.6

29.3

32.9

27.7

27.5

26.5

30.0

33.2

S.C.

23.9

23.2

19.6

19.7

16.4

25.7

25.9

21.8

22.4

17.8

27.6

28.6

24.0

25.0

19.1

K.W.

2.3

2.3

2.3

2.4

2.4

2.3

2.3

2.3

2.4

2.4

2.4

2.4

2.4

2.4

2.5

105

T.C.

22.5

23.6

22.9

26.2

29.8

24.1

24.6

23.8

26.8

30.1

25.7

25.5

24.6

27.3

30.3

S.C.

22.4

22.1

18.6

18.9

15.4

24.0

24.2

20.9

21.4

16.8

25.6

26.4

23.2

23.9

18.2

K.W.

2.5

2.5

2.5

2.5

2.6

2.5

2.5

2.5

2.6

2.6

2.6

2.6

2.5

2.6

2.6

115

T.C.

21.0

21.8

21.0

23.9

27.1

22.4

22.7

21.9

24.3

27.3

23.8

23.6

22.9

24.7

27.6

S.C.

21.0

21.0

17.6

18.2

14.5

22.3

22.6

20.1

20.5

15.9

23.7

24.2

22.5

22.8

17.2

K.W.

2.6

2.6

2.6

2.7

2.8

2.7

2.7

2.6

2.7

2.8

2.7

2.7

2.7

2.8

2.8

125

T.C.

19.6

19.9

19.1

21.5

24.3

20.7

20.8

20.1

21.8

24.5

21.8

21.7

21.1

22.1

24.8

S.C.

19.5

19.9

16.7

17.4

13.6

20.6

20.9

19.2

19.5

14.9

21.7

22.0

21.7

21.7

16.3

K.W.

2.8

2.8

2.8

2.9

3.0

2.9

2.9

2.8

2.9

3.0

2.9

2.9

2.8

2.9

3.0

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
**

For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.

Air Handler

Coil

T.C.

S.C.

KW

MA12B

FC/MC35B

1.00

1.00

1.00

MA12B

FC/MC42B

1.00

1.00

1.00

AHP30

1.00

0.97

1.00

F*FP040

0.99

0.97

0.99

MV12B*

FC/MC35B

1.02

1.00

0.98

MV12B*

FC/MC42B

1.02

1.00

0.98

MV16C*

FC/MC35C

1.02

1.00

0.98

MV16C*

FC/MC42C

1.02

1.00

0.98

AV36*

1.02

1.00

0.98

FC/MC/PC/UC42

1.00

1.00

1.00

HC36

0.99

0.97

0.99

HD36

1.01

1.00

1.01

Variable Speed
Furnace *

Coil

T.C.

S.C.

KW

(F,L)L8VB16

FC/MC/PC35B

1.02

1.01

0.98

FL9(C,V)B12

FC/MC/PC35B

1.02

1.01

0.98

(F,L)L8VC16

FC/MC/PC35C

1.02

1.00

0.98

FL9(C,V)C16

FC/MC/PC35C

1.02

1.01

0.98

(F,L)L8VB16

FC/MC/PC42B

1.02

1.01

0.98

FL9(C,V)B12

FC/MC/PC42B

1.02

1.01

0.98

(F,L)L8VC16

FC/MC/PC42C

1.02

1.00

0.98

FL9(C,V)C16

FC/MC/PC42C

1.02

1.01

0.98

(F,L)L8VB16

HC36

1.02

1.01

0.98

FL9(C,V)B12

HC36

1.02

1.01

0.98

(F,L)L8VB16

HD36

1.02

1.01

0.98

FL9(C,V)B12

HD36

1.02

1.01

0.98