* This loose coil match does not achieve 13 SEER.

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-

connecting line tubing.

2. Verify the orifice size and the additional charge required for the specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base charge (as shipped) + adder for

evaporator + adder for line set.

5. If the orifice in the evaporator was changed, verify the evaporator nameplate has been marked with the correct orifice/TXV size.

HD24A3X

0

HD36B3X

0

9

HD48C3X

14

HD60D3X

7

7

AHP18B3X

0

AHP24B3X

0

AHP30B3X

0

AHP36C3X

9

AHP42C3X

9

AHP/SHP48D3X

14

7

AHP/SHP60D3X

7

7

AV24B3X

0

0

AV36C3X

0

9

AV/SV48D3X

14

7

AV/SV60D3X

14

7

7

F*FP024H06T2A

0

F*FP030H06T2A

0

F*FP040H06T2A

0

9

F*FP042H06T2A

9

F*FV060H06T2C

7

7

FOOTNOTES:

1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)

Outdoor Unit

EABD-F018S

EABD-F024S

EABD-F030S

EABD-F036S

EABD-F042S

EABD-F048S

EABD-F060S

Required TXV

1TVM2A1

1TVM2A1

1TVM2A1

1TVM2A1

1TVM2C1

1TVM2C1

1TVM2C1

Factory Charge, lbs-oz

7 - 1

6 - 9

8 - 9

8 - 7

8 - 7

12 - 8

16 - 7

Indoor Coil

1,2

Additional Charge, Oz