York E*BD-(T User Manual

Page 5

Advertising
background image

246819-BTG-H-0208

Unitary Products Group

5

All dimensions are in inches. They are subject to change with-
out notice. Certified dimensions will be provided upon request.

Physical and Electrical Data - 3 Phase

MODEL

EABD-

T030S

EABD-

T036S

EABD-

T042S

EABD-

T048S

EABD-

T060S

EABD-

W030S

EABD-

W036S

EABD-

W042S

EABD-

W048S

EABD-

W060S

Unit Supply Voltage

208-230V, 3

φ, 60Hz

460V, 3

φ, 60Hz

Normal Voltage Range

1

187 to 252

432 to 532

Minimum Circuit Ampacity

12.1

14.3

14.4

20.2

23.1

5.6

6.9

7.2

9.5

11.2

Max. Overcurrent Device Amps

2

20

20

20

35

40

15

15

15

15

15

Min. Overcurrent Device Amps

3

15

15

15

25

25

15

15

15

15

15

Compressor Type

Recip

Recip

Recip

Scroll

Scroll

Recip

Recip

Recip

Scroll

Scroll

Compressor Amps

Rated Load

8.5

10.2

10.4

15.0

16

3.9

4.9

6.1

6.1

8

Locked Rotor

62

72

71

95

123

30

45

45

45

70

Crankcase Heater

Yes

Yes

Yes

No

No

Yes

Yes

Yes

No

No

Fan Motor Amps

Rated Load

1.5

1.5

1.5

1.5

1.5

0.7

0.7

0.7

0.7

0.7

Fan Diameter Inches

22

22

22

24

24

22

22

22

24

24

Fan Motor

Rated HP

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

Nominal RPM

850

850

850

850

850

850

850

850

850

850

Nominal CFM

3450

3500

3500

3400

3500

3450

3500

3500

3400

3500

Coil

Face Area Sq. Ft.

20.96

23.58

23.58

24.00

27.00

20.96

23.58

23.58

24.00

27.00

Rows Deep

1

1

1

2

2

1

1

1

2

2

Fin / Inches

22

22

22

18

18

22

22

22

18

18

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

7/8

7/8

7/8

7/8

1-1/8

7/8

7/8

7/8

7/8

1-1/8

Unit Charge (Lbs. - Oz.)

4

8 - 7

8 - 7

8 - 7

12 - 8

16 - 7

8 - 7

8 - 7

8 - 7

12 - 8

16 - 7

Charge Per Foot, Oz.

0.70

0.70

0.70

0.70

0.76

0.70

0.70

0.70

0.70

0.78

Operating Weight Lbs.

196

208

208

250

294

196

208

208

250

294

1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than

15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. If line exceeds 25
feet, you may refer to publications software 036-68001-001 for proper line sizing.

C

B

A

DIMENSIONS

Unit

Model

Dimensions

(Inches)

Refrigerant Connection

Service Valve Size

A

1

1. Including Fan Guard.
* Adapter fitting required for 1-1/8” line set.

B

C

Liquid

Vapor

030

35

37

27

3/8”

7/8”

036

39

37

27

042

39

37

27

048

34

43

32

060

38

43

32

7/8”*

Advertising