8. Safety Circuit Shutdown Messages

PNEG-1935 Vision Hybrid for Portable Dryers

55

Main I/O Shutdown Messages

0E01 - Main I/O - Primary Unload Motor Overload

This message indicates that the unload motor overload has been tripped in the upper control box. This
indicates that 12 VDC has been lost to terminal J1-02 on the Input/Output board. Push the red button on
the overload to reset this error. This is caused by the motor operating under too much load, which uses
more current (amperage). If the problem continues, then check the motor to make sure it is not being
overworked. You may need to call an electrician to measure the motor’s full load amps (FLA).

0E02 - Main I/O - Primary Load Motor Overload

This message indicates that the motor overload has tripped on the load motor overload located in the
upper control box. This can occur if the safety 12 VDC to terminal J1-03 on the Input/Output board is loose.
Push the red button on the overload to reset this error. This is caused by the motor operating under too
much load, which uses more current (amperage). If the problem continues, then check the motor to
make sure it is not being overworked. You may need to call an electrician to measure the motor’s
full load amps (FLA).

0E03 - Main I/O - Auxiliary Unload Motor Overload

This message indicates that the motor overload relay has been tripped on the auxiliary unload motor circuit
located in the upper control box. This can occur if safety 12 VDC to terminal J1-04 on the Input/output
board is loose. Push the red button on the overload to reset this error. This is caused by the motor
operating under too much load, which uses more current (amperage). If the problem reoccurs, then check
the motor to make sure it is not being overworked. You may need to call an electrician to measure the
motor’s full load amps (FLA).

0E04 - Main I/O - Auxiliary Load Motor Overload

This message indicates that the motor overload relay has tripped on the auxiliary load motor circuit located
in the upper control box. This can occur if safety 12 VDC to terminal J1-05 on the Input/Output board is
loose. Push the red button on the overload to reset this error. This is caused by the motor operating under
too much load, which uses more current (amperage). If the problem reoccurs, then check the motor to
make sure it is not being overworked. You may need to call an electrician to measure the motor’s full load
amps (FLA).

0E05 - Main I/O - Rear Discharge Door Open

This message indicates that the lid on the grain discharge box has opened, indicating that either the grain
is not being taken away fast enough or the take away auger system connected to the dryer may be causing
the problem. This can also occur if this safety loses 12 VDC to terminal J1-08 on the Input/Output board.

0E06 - Main I/O - Air System Failure

This message indicates that a shutdown has occurred due to an air system that was installed with an
integral safety switch that was in the unit. The air system safety connections are located in the upper
control box on the terminal strip. This can occur if safety 12 VDC to terminal J1-10 on the Input/Output
board is loose. This input is on the terminal strip when it leaves the factory and is usually installed in the
field by a qualified electrician.