2 navigation on the control keypad, 2 factory parameters – R&M Materials Handling ELECTRIC CHAIN HOISTS LoadMate Chain Hoist LM 10 Stepless User Manual

Page 38

Advertising
background image

LM10 STEPLESS I&M MANUAL/EN/11.30.2010


38/99

This document and the information contained herein, is the exclusive property of R&M Materials Handling, Inc., and represents a non-public, confidential and proprietary trade secret that
may not be reproduced, disclosed to third parties, altered or otherwise employed in any manner whatsoever without the express written consent of R&M Materials Handling, Inc.
Copyright © (2010) R&M Materials Handling, Inc. All rights reserved.

7.5.7.2 Navigation on the control keypad

Editing numerical settings

m

WARNING! Changing parameter settings during running may cause a hazardous situation.
Parameter settings must not be changed during running.

a) Pushing ► button takes you into the edit mode.

As an indication, the parameter value starts to blink.

b) Two different methods are available to change values.

One is to set with ▲▼buttons till your desired value.

Another is to select desired digit and edit it. First push ► button,

the digit before decimal point will blink, then use ►◄ buttons to select

desired digit, set value with ▲ ▼ buttons.

C) Accept and exit with “reset/enter” button.

7.5.8 Storing and restoring parameters

7.5.8.1 User parameters

File “User parameters” is stored in inverter’s control unit.

User parameters should be saved after final set up.

The whole customized parameter set can be stored with parameter P3.3.1 by option 1(=Store user
parameters)

Select Option number 1, then press “Enter”

User parameters can be restored with parameter P3.3.1 by option 2 (=Load user parameters).

Select Option number 2, then press “Enter”

After restoring always check the motor parameters.

7.5.8.2 Factory parameters

File “Factory parameters” is stored in inverter’s control unit.

Factory parameters are saved at the factory according to the order and they should not be changed,
the values are the same as those in parameter list delivered with inverter.

Factory parameters can be restored with parameter P3.3.1 by option 4 (=Load factory parameters).

Select Option number 4, then press “Enter”

After restoring always check the motor parameters.

I/O term

V

I/O term

V

I/O term

V

enter

reset

enter

reset

I/O term

V

Advertising