G1.3 I/O Parameters

Code

Name

Min

Max

Unit

Description

P1.3.1

ROA1

0

12

State of relay output ROA1 (See Chapter "Relay output")
0 = Not Used
1 = Fault
2 = External Brake Control
3 = Run, current is fed to the motor, default
4 = Drive is ready to operate
5 = Drive is NOT ready to operate
6 = Fan. DC-link voltage is above braking chopper operating value –70V. Relay
is closed minimum 300s.
7 = Emergency Stop, relay is activated in case of faults F1 Overcurrent, F2
Overvoltage, F3 Earth Fault. Relay is deactivated when the power is switched
off.
8 = Reverse Plugging. Direction request is different than direction of actual
frequency.
9 = At Speed. The Drive has reached the speed reference request.
10 = S2 Active. Motor actual speed direction is S2.
11 = Temp1. Relay is activated when temperature is 20ºC (68F) or below.
Relay is inactivated when temperature is 23ºC (73F) or above.
12 = Temp2. Relay is activated when temperature is 40ºC (104F) or above.
Relay is inactivated when temperature is 37ºC (98F) or below.

P1.3.2

Ain1 Minimum
Voltage

0.000

10.000

V

Minimum value of analog input Ain1 for AU-control

P1.3.3

Ain1 Maximum
Voltage

0.000

10.000

V

Maximum value of analog input Ain1 for AU-control

P1.3.4

Aout Function

0

5

0 = Not Used
1 = Motor Freq (100%*Normal Motor Frequency)
2 = Motor Curr (100%*Normal Motor Current)
3 = Motor Volt (100%*Normal Motor Voltage)
4 = DC-link Volt (1000V)
5 = MotorFreqABS (Absolute value of Motor Frequency)

P1.3.5

Aout Zero Current

0.00

Aout
Nom
Curr

mA

P1.3.6

Aout Nominal
Current

Aout
Zero
Curr

100.00

mA

G1.4 Not used

Code

Name

Min

Max

Unit

Description

P1.4.1

0 = Default value
1 = must not be used
2 = must not be used

P1.4.2

Not used

P1.4.3

Not used

P1.4.4

Not used

P1.4.5

Not used

G1.5 Expert

Code

Name

Min

Max

Unit

Description

P1.5.1

Slowdown Mode

0

2

0 = Slow
1 = Fast, default
2 = Fast Power Up (See Chapter "Slowdown-limit operation")

P1.5.2

S-Curve

0.00

0.50

s

The start and end of the acceleration and end of deceleration ramp can be
smoothed with this parameter. Setting value 0.00-0.50 seconds for this
parameter produces an S-shaped acceleration/deceleration.

P1.5.3

Ramp Stretching

0.00

50.0

See Chapter "Ramp Stretching". Not used in hoisting

P1.5.4

Switching Frequency

Must not be changed from factory setting

P1.5.5

Brake Chopper

1, default
Must not be changed