Programmable alarms – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual
Page 184

GEI-100332Ga
——— FUNCTION DESCRIPTION ———
6
56
Dim factor num
4
Dim factor den
3
Dim factor text
F/min (bottles per minute)
Example of the face value factor
Normally the reference value has a resolution of 1 rpm. In order to exploit the available resolution, the face
value factor is used.
The motor speed range required is, for example, 0...1500 rpm. A more accurate resolution (i.e. 1/4 revolution)
can be obtained by setting hte face value factor to 1/4.
The value 4 000 is entered, for example, in order to select 1000 rpm This is then multiplied with the face value
factor to give the value 1000 rpm.
Face value num
1
Face value den
4
6.11.7. programmable alarms
CONFIGURATION
Prog alarms
Failure supply
[194]
Latch
[195]
Ok relay open
Undervoltage
[481]
Undervolt thr [V]
[357]
Latch
[358]
Ok relay open
[470]
Hold off time [ms]
[359]
Restart time [ms]
Overvoltage
[203]
Activity
[361]
Latch
[362]
Ok relay open
[482]
Hold off time [ms]
[483]
Restart time [ms]
Overspeed
[1426]
Overspeed thr [rpm]
[1422]
Activity
[1421]
Latch
[1423]
Ok relay open
[1424]
Hold off time [ms]
[1425]
Restart time [ms]
Heatsink
[368]
Activity
[370]
Ok relay open
Overtemp motor
[365]
Activity