DV-300 Adjustable Speed Drives
——— PARAMETER LISTS ———
10
17
Parameter
No.
Format
Value
Access via
min
max
Factory
American
Factory
European
Keyp.
RS485/
BUS/
Opt2-M
Term.
Opt2-A/
PDC
CONFIGURATION \ Prog alarms \ Bus loss
Activity
Ignore
Warning
Disable drive
Quick stop
Normal stop
Curr lim stop
634
U16
0
5
Disable
drive
Disable
drive
ü
R/Z
0
1
2
3
4
5
-
-
Latch
ON
OFF
633
U16
0
1
ON
ON
ü
R/Z
1
0
-
-
Ok relay open
ON
OFF
635
I16
0
1
ON
ON
ü
R/W
1
0
-
-
Hold off time [ms]
636
U16
0
10000
0
0
ü
R/W
-
-
Restart time [ms]
637
U16
0
10000
0
0
ü
R/W
-
-
CONFIGURATION \ Prog alarms \ Hw opt1 failure
Activity
Warning
Disable drive
Quick stop
Normal stop
Curr lim stop
386
U16
1
5
Disable
drive
Disable
drive
ü
R/Z
1
2
3
4
5
-
-
Ok relay open
ON
OFF
387
I16
0
1
ON
ON
ü
R/W
1
0
-
-
CONFIGURATION \ Prog alarms \ Enable seq err
Activity
Ignore
Disable drive
728
U16
0
2
Disable
drive
Disable
drive
ü
R/Z
0
2
-
-
Latch
ON
OFF
729
U16
0
1
ON
ON
ü
R/Z
1
0
-
-
Ok relay open
ON
OFF
730
U16
0
1
ON
ON
ü
R/W
1
0
-
-
CONFIGURATION \ Set serial comm
Device address
319
U16
0
127
0
0
ü
R/Z
-
-
Ser answer delay
408
U16
0
900
0
0
ü
R/W
--
---
Ser protocol sel
SLINK3
MODBUS RTU
JBUS
323
U16
0
2
SLINK3
(0)
SLINK3
(0)
ü
R/W
0
1
2
--
---
Ser baudrate sel
19200
9600
4800
2400
1200
326
U16
0
4
9600
(1)
9600
(1)
ü
R/W
0
1
2
3
4
--
---
CONFIGURATION
Pword 1
85
I32
0
99999
0
0
ü
W
-
-