Xylem IMVIT R01 Model VIT Vertical Industrial Turbine Pumps User Manual

Page 18

Advertising
background image

18

DIRECT PULL METHOD
1. The upper end of the tube may be pulled by the

hoist to obtain the predetermined tension value.

This requires the use of a dynamometer scale and

an adapter fitting to grip the tube. TUBE TENSION

ADAPTER AVAILABLE THROUGH FACTORY.

With the tension plate installed manually but

not tightened, thread the special fitting onto the

top of the tube to full engagement. Attach the

dynamometer scale to the fitting, and connect the

upper end of the scale to the hoist hook. Operate

the hoist hook to apply the required tension. This

should pull the tension plate off the discharge head.

Manually thread the tension plate to reset it. Release

tension, remove dynamometer scale and special

fitting.

WRENCHING METHOD
1. If a dynamometer is not available, the tube can

be tensioned by wrenching the tube tension

plate. Make up a spanner wrench to straddle the

projecting threaded tube end and to engage the tube

tension plate capscrew holes by two lugs. Torque

the tension plate to take all the slack out of the shaft

tubing and induce a reasonable amount of tension

by turning the tension plate counterclockwise. For

tubing 2½” (63.5mm) and larger, an individual's full

strength on a 3 foot (915mm) lever arm is sufficient.

For smaller sizes, less pull must be exercised.

Figure 10

NOTE: Do not turn clockwise to align holes in tension

plate and discharge head.

INSTALLING TENSION NUT
1. (See Figure 10). Install capscrews (760) in the

tension plate. Pour one pint of oil down the oil

tube. Note: Factory assembled unit has no oil in it.

Oil must added in the field.

2. Install packing (620) in the tension plate and thread

the tension nut (626), tightening it firmly against the

packing.

3. If a packed type tension nut (626) is used (for water

flush), install packing (620), packing gland (618)

and secure with stud (734) and nut (735). Screw nut

finger tight. Install line assembly (635) and connect

to flush liquid supply (see Figure 10).

Be sure that the top of the enclosing tube

does not interference with the tension nut.

4. If the top of the tube interferes with the tension nut,

determine the distance, if the tube is too long or too

short. If the tube is too short, it must be replaced

with a longer tube of the correct length. If the tube

is too long, it must be cut to the correct length and

re-threaded. Reinstall and re-level pump.

LUBRICATION SYSTEM
1. Connect solenoid valve (if provided), oil lines, and

fill the oil reservoir with oil.

2. Check the lubricator feed and see that the oil

reservoir is flowing freely. (In the case of a solenoid

valve, temporary power connections are required.)

Set the proper drops per minute on the regulator.

Table 2 shows recommended regulator setting.

TABLE 2 – Regulator Setting

Shaft Size

Basic drops Additional drops

(in.)

per minute

per minute per

100 ft. setting

0.75 - 1.18

5

2

1.50 - 1.68

7

3

1.94 - 2.43

10

4

2.68 and larger

12

5

INSTALLING THE TENSION PLATE WITH BRONZE

TENSION NUT
Assemble Tension Plate Assembly as shown in Figure 11.
1. Remove the lock bolt (636) and o-ring (621).

Thoroughly clean the tension plate (625) include the

o-ring groove. Lightly grease the o-ring and re-install

it.

2. Clean the surface of the discharge head where the

tension plate will be mounted and remove any nicks

or burrs with a fine flat file. Clean the O.D. of the

tube nipple. Carefully install the tension plate and

gasket (779). Evenly tighten the mounting capscrews

(759F).

3. Pour one pint of recommended oil down the tube

nipple (629). (See page 27 for recommended

lubricants.) Note: Factory assembled unit has no oil

in it. Oil must be added in the field.

CAUTION

Advertising