10 Maintenance

Although very little maintenance is required with Argus systems, routine checks and adjustments are
recommended to ensure optimum system performance. Qualified service personnel should do repairs.

The following table lists a few maintenance procedures for this system. These procedures should be performed at
least once a year.

WARNING: HIGH VOLTAGE AND SHOCK HAZARD.

Use extreme care when working inside the enclosure/shelf while the system is energized.
Do not make contact with live components or parts.

Circuit cards, including RAM chips, can be damaged by static electricity. Always wear a grounded
wrist strap when handling or installing circuit cards.

Procedure

Date Completed

Clean ventilation openings

Inspect all system connections (re-torque as necessary)

Verify alarm/control settings

Verify alarm relay operation

Table A–Sample maintenance log

10.1 Fan and Filter

IMPORTANT
It is recommended that filter maintenance (every two to six months) be promptly scheduled, to
eliminate failure possibilities.

10.2 Batteries

It is recommended that checks are made every three months for battery voltage, conductance, temperature,
impedance, connections, etc.

See battery manual for general maintenance information.

10.3 Enclosure

Surge

Arrestor

The surge arrestor should be checked every three to five years for failure. Lamp indicator signals replacement
required.