Specifications for Argus’ Te25xh Outdoor Power Enclosure

Argus Technologies Ltd.

029-006-B1 Rev D WC

Printed in Canada. © 2006 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved.

Page 1 of 2

Mechanical

Dimensions (minimum):

914mm H x 544mm W x 518mm D; see outline drawings,
(36" H x 21.4" W x 20.4" D)
[dimensions vary depending on mounting and other options ordered]


Mounting:

Ground/pedestal or pole


Weight (no batteries/rectifiers): 45.6 kg (100.5 lb.), no riser

55.1 kg (121.5 lb.), with riser
52.9 kg (116.6 lb.), pole mount


Cooling: Fan

cooled


Enclosure: Aluminum,

5052-H32


Internal Rack (optional):

19”, 4RU


Environmental

Operating Temperature:

-40 to +46°C

(-40 to 115°F)


Storage Temperature:

-40 to +85°C
(-40 to +185°F)


Humidity:

0 to 95% non-condensing


Elevation: 3600m,

see

Operating Temperature

(12,000 feet)


Weather Tightness:

NEMA Type 3R
NEMA 4 with closed loop cooling (air exchanger or air conditioner option)


Thermal Performance:

14.6°C above ambient of 24°C @400W

1

[single cooling fan]

(26.3°C above ambient of 75.2°C)
11.6°C above ambient of 24°C @400W [dual cooling fans]
(20.8°C above ambient of 75.2°C)


Regulatory Approvals

Enclosure Ratings:

CSA/UL Type 3R

Product Safety:

CSA/UL 60950


1

Simulated heat load inside enclosure.

Advertising