Alpha Technologies Continuity: 1000_2000_3000 User Manual

Page 20

Advertising
background image

0170009-J0 Rev B

18

3. When serial communications are established between the UPS and your computer, the following

screen appears.

2. In the first UPS Setting Tool screen, select your computer's Com Port from the drop down menu.

4. Configure the settings as follows:

System Voltage Selection

Select Input Voltage 110V* or 220V*

Voltage Configurations

Select UPS Output Voltage

200V/208V/220V/230V/240V or

100V/110V/115V/120V/127V

UPS Modes

Select Normal/ CF50** /CF60** Mode

Output Voltage Fine Tuning

Output Voltage Regulation from 0 to ~±3%

Bypass Voltage Windows

Sensitivity Low

Sensitivity High

120V System

90V~130V

97V~130V

230V System

180V~260V

194V~260V

Syn-Frequency Window

Select 3Hz/ 1Hz Inverter Freq synchronizing range

Com Port

Displays curent PC Com Port

*Select 110V for a 120V input; select 220V for a 230V input
**CF50/ CF60 = Frequency Converter mode 50 to 60Hz or vice versa

5. Click Write to confirm the configuration settings. The UPS beeps twice if the new settings are saved

successfully. Note that the settings do not take effect until you restart the UPS at the end of this

section.