1.  Important Safety Instructions

1.1  Important Information

SAVE THESE INSTRUCTIONS – This manual contains important Instructions that must be followed during

the installation and maintenance of the UPS.
• The UPS has its own internal energy source (battery). A voltage may be present at the output

terminals even when no AC input power is available.

• This UPS is equipped with an EMI filter. To prevent potential leakage current hazard, ensure that the

AC main supply is securely grounded.

• Make sure that the AC utility outlet is correctly grounded.
• Make sure that the input voltage to the UPS matches the rating on its name plate. Use a certified

input power cable with the correct plugs and sockets for the appropriate voltage system.

• Install the UPS indoors only as it is not designed for outdoor use. Install in a temperature-controlled

indoor area free of conductive contaminants

• To prevent the UPS from overheating, keep all ventilation openings unobstructed. Do not place

anything on top of the UPS. Keep the UPS rear panel at least 20 cm away from the wall or other

objects.

• Units are considered acceptable for use in a maximum ambient of 40°C. Make sure the UPS is

installed in an appropriate environment—0 to 40

ºC (32 to 104ºF) ambient temperature, and 30 to

90% relative humidity (non-condensing).

• Do not install the UPS in direct sunlight. Failure of the batteries under these conditions may void the

warranty.

• Do not install in a inflammable or hazardous environment.
• Dusty, corrosive, or salty environments can damage the UPS.
• Install the UPS away from objects that give off excessive heat and areas that are excessively wet.
• Do not install the UPS in an environment with sparks, smoke or gas. Not for use in a computer room

as defined in the Standard for the Protection of Electronic Computer/Data processing Equipment,

ANSI/NFPA 75.

• The entrance of liquids or foreign objects into the UPS will void the warranty.
• The battery will gradually discharge if the system is unused for extended periods.
• If unused, recharge the UPS every 2 to 3 months. Neglecting to do so will void the warranty. The

batteries charge automatically and are kept in good condition if the UPS is installed and used.

• This UPS supports electronic equipment in offices, telecommunications, process control, medical

and security applications. Only authorized personnel must install the UPS in the following locations:
• Medical applications directly related to human life
• Elevators, metro (subway) system or any other equipment related to human safety
• Public security system or critical computer systems

• Always switch off the UPS and disconnect the batteries before relocating the UPS. It may cause

electrical shocks if the output is not completely switched off.

• Do not open the UPS—there are no serviceable parts inside. Opening the UPS will void the warranty.
• Do not repair the UPS yourself Contact your local supplier. Opening the UPS will void the warranty.

1.2  Storage Instructions

Store the UPS in a location where the temperature ranges between -15

ºC (+5ºF) to 40ºC (104ºF).

For extended storage in moderate climates, charge the batteries for 12 hours every 3 months. Connect

the UPS to the utility supply and switch on the input breaker located at UPS rear panel. Repeat this pro-

cedure every 2 months if the ambient storage temperature is above 30

ºC (86ºF).