A-2  Utility is Normal

When the utility voltage is normal, the AC power is rectified to DC power, which is then fed into the in-

verter. The charger is switched to charge the batteries. The inverter transforms the DC power to clean AC

power that supplies the loads. The

,

,and

LEDs are illuminated.

A-3  Utility Power is Abnormal/Absent

The working principle of the UPS when the utility power is abnormal is illustrated below:When the utility

power is abnormal (under voltage, over voltage or absent), the UPS converts battery power to AC power

through the DC-DC and DC-AC inverter. It also disables the AC-DC and charger sections. This happens

instantaneously as the abnormality is detected.

1. When utility power returns to normal, the UPS switches to normal mode as explained in the previous

section.

2. During a utility outage, the figure above illustrated the operation of the UPS. When the batteries are

depleted, the buzzer beeps continuously until the unit is shutdown. The UPS low battery protection

shuts off the output after a preset threshold to avoid over-draining the batteries. The

LOW

(battery

low)&

(battery abnormal) symbols appear on the LCD until the UPS is completely shut off. The

UPS re-starts automatically when the utility is restored.

A-4  Overload Condition

1. Most electronic and IT equipment draw an inrush current when turned on. The amplitude and

duration of the inrush current varies depending on the equipment. Some inrush currents can be

as high as six times the rated capacity while some equipment produce negligible inrush currents.

To prevent severe inrush current damage to the inverter, the UPS is equipped with an electronic

overload protection feature. If the UPS load is between 105 and 120% of its capacity, it switches to

the bypass mode after 30 seconds to protect the inverter. If the overload condition is removed, the

UPS switches back to inverter mode. If the UPS load is more than 150% of its capacity, the inverter

shuts down immediately.

2. The UPS bypass loop is also equipped with overload protection. Its overload capacity is illustrated by

the graphs and table below.