5.  Operation

5.1  Front Panel LCD

Table C — LCD Panel Description

Item

Description

1

LCD display

2

Green Utility LED illuminates to indicate that the Utility input voltage is within the range

80Vac~144Vac, or 160Vac~288Vac; the LED flashes to indicate that the Utility input

voltage is within the range 60Vac~79Vac, or 120Vac~159Vac.

3, 4

Green LEDs for Programmable Outlet 1 and Programmable Outlet 2 illuminate to

indicate power is available at the outlets.

5

Amber LED illuminates to indicate the Bypass input is normal.

6

Red Fault LED

7

ON/Alarm silence button

8

OFF button

9

Special functions log in/out

10

SCROLL DOWN key: Go to next page

11

SCROLL UP key, Go to previous page or change the setting of the UPS

12

Enter key: to confirm the change of a UPS setting

Manual

Bypass

Press and hold the ON key (7) and the SCROLL UP key (11) simultaneously for

~3 seconds to transfer from Inverter to Bypass ( the amber Bypass LED blinks

continuously and the buzzer beeps intermittently)
OR
from Bypass to Inverter, when the UPS is on Line Mode and the Bypass Voltage

Window is Normal.

Symbols

Utility Low
Utility High
Line

Site Wiring/ Ground Fault
Battery Abnormal
UPS Overload
UPS in Service Mode
Bypass

LINE/

LOAD

Utility or Bypass Source

Er**

Error Codes (see Section

6.3)

OFF

UPS Shutoff

FAIL

UPS Abnormal Lock

Figure 1 — Front Panel LCD