Alpha Technologies Continuity: 1000_2000_3000 User Manual

Page 39

Advertising
background image

37

0170009-J0 Rev B

Output

Output -

INV mode

Voltage

115V

115V, adjustable to 100/110/115/120/127

230V

230V, adjustable to 200/208/220/230/240

Voltage Regulation

≤ ± 1% until low battery warning

Frequency(Synchronized

Range)

3Hz or 1Hz (setting by software)

Frequency(Battery Mode)

±0.1% (0.05~0.06Hz) unless synchronized to line

Current

Crest Factor

PF=0.8

2.7:1

Harmonic Distortion

1KVA,2KVA, 3KVA ≤ 3% THD(Linear Load)

1.5KVA ≤ 4% THD(Linear Load)

≤ 7% THD(Non-Linear Load)

Transient Response (ms)

≤ 60ms/±5%

Waveform

Pure sine wave

Efficiency

To AC Mode (Full load)

85%

85%

88%

To Battery Mode (Full load) 83%

83%

85%

Battery Parameters

Model number

AIDCO 1 kVA

AIDCO 2 kVA

AIDCO 3 kVA

Type

12V/7.2Ah

12V/7.2Ah

12V/9Ah

Number of Batteries

3

6

6

Backup Time (Full Load)

PF=0.8

>5min.

>5min.

>4min.

Recharging Time

4 Hours to 90%

Charging Current (Max.)

1.8A

2.16A

2.7A

Charging Voltage

41.0Vdc ±0.5V

82.0VDC ±0.5V

82.0VDC ±0.5V

Hot Swappable Battery

Yes

Internal battery

Yes

DC leakage current

≤ 30uA (±10uA) with no AC applied and the unit in the off

position

Battery type

Sealed, non-spill, maintenance-free, lead acid

Transfer Time

AC to DC

Zero

Inverter to Bypass

2.5ms (Typical)

Zero

DC Start

Yes

Self Diagnostics

By button on the panel or Software Control

Front Panel

LED

Load Level/Battery Level/ Battery Mode/ Normal Mode/
Bypass Mode/ Self-Test/ Weak/Bad Battery/Site Wiring Fault/
Fault/ Overload/Programmable Outlet1//Programmable

Outlet2

Key

ON Button/ OFF Button/ (Test/Alarm Reset Button)

Advertising