Table F — Specifications
Model
AIDCO 1kVA
AIDCO 2kVA
AIDCO 3kVA
VA rating
Apparent Output Power
1000VA
2000VA
3000VA
Active Output Power
PF=0.8
800Watts
1600Watts
2400Watts
Power Factor
0.8
Topology
Double conversion On-Line
Type
Rack/Tower
Agency Approvals
115V Models: UL, cUL, FCC
230V Models: CE
Input
Voltage Window
115V
60/70/80 - 144VAC
230V
120/140/160 - 288VAC
Voltage
Range
Based on load percentage (0~33/33~66/66~100%)
Low Line
Transfer
115V
60/70/80VAC
230V
120/140/160VAC
Low Line
Comeback
115V
85VAC
230V
170VAC
High Line
Transfer
115V
144VAC
230V
288VAC
High Line
Comeback
115V
139VAC
230V
278VAC
Frequency
50/60 Hz auto-select, ± 5Hz
Phase
Single phase with ground
Power Factor
>0.99 at full rated linear load
Transfer time
0 ms typical
Waveform
115V
≤ 5mA
230V
≤ 3.5mA
Surge protection
115V
400 joules
230V
300 joules
8. Specifications