Table E — Troubleshooting Table

Situation

Error Indication

Solution

UPS Fault LED

Refer to Table D for error

codes).

Er05

Check battery connection.

Measure Battery voltage to ensure batteries are

charged or healthy. Recharge batteries for 4 hours

if necessary.

Simulate Utility outage to verify if UPS is able to

provide DC back-up.

Otherwise consult your local dealer right away.

Overload

Disconnect some non critical loads from the UPS

output until overload ceases.

Check for short circuit between cables due to

broken cable insulator. Replace the cables in

necessary.

Er11 (UPS over

Temperature)

Remove any objects obstructing the ventilation

louvers.

Verify if the cooling fans are working properly.

Contact your local dealer to replace the fans if

necessary.

Site wiring/

Ground fault

Verify if the L and N phase of the Utility AC source

is incorrectly wired or if the Ground-Neutral Voltage

exceeds the limits

Er14 (Fans out

of order)

Verify ventilating fans are functioning.

Do not attempt to replace the fans by yourself.

Contact your local dealer for replacement

Other error

codes

Consult your local dealer for assistance.

UPS fails to provide

battery backup or its back

up time is shorter than its

intended performance.

If the backup time remains unsatisfactory after 4

hours of charging, contact your local dealer for

battery replacement.

UPS is normal but no

Output to load

Check that all power cords are properly connected.

If problem persists, consult your local dealer for

technical assistance.

The UPS switches to

battery mode then back

to Utility mode, when

a connected device is

turned on. Or,
The UPS switches back

and forth between battery

and utility.

If a power bar is connected to the UPS, Do not use

the power bar.

Check for damage to the utility wall receptacle,

cable, or plug. replace if necessary.