Protection

Overload

(AC Mode )
<105% continuous
>106%~120% for 30 sec transfer to bypass
>121%~150% for 10 sec transfer to bypass
>150% for immediate transfer to bypass
Buzzer continuously alarms.
(Battery Mode)
<105% continuous
>106%~120% for 30 sec shut down
>121%~150% for 10 sec shut down
>150% for immediate shut down
Buzzer continuously alarms.
(Bypass Mode)
<105% continuous
>106%~120% for 250 sec shut down
>121%~130% for 125 sec shut down
>131%~135% for 50 sec shut down
>136%~145% for 20 sec shut down
>146%~148% for 5 sec shut down
>149%~157% for 2 sec shut down
>158%~176% for 1 sec shut down
>177%~187% for 0.32 sec shut down
>188% for 0.16 sec shut down
Buzzer continuously alarms.

Short Circuit

Bypass mode : Input Fuse/Input Breaker
Normal Mode: Output Breaker/Electronic Circuit
Battery Mode: Output Breaker/Electronic Circuit

Battery

ABDM

EPO

UPS shuts down immediately

Over Temperature

Normal Mode

Transfer to Bypass Mode

Battery Mode

UPS shuts down immediately

Audible Alarm

Battery Mode

Sounding once every 1.5 sec

Low Battery

Sounding once every 0.2 sec

Overload

Sounding once every 3 sec

Fault

Continuously Sounding (or Sounding once every 3 second)

Environmental

Operating Temperature

+32°F to + 104°C (0°C to + 40°C)

Storage Temperature

+5°F to + 104°F (-15°C to + 40°C)

Relative Humidity

0% to 90%, non-condensing

Noise Level

<50dBA