Alpha Technologies Continuity: 1000_2000_3000 User Manual

Page 27

Advertising
background image

25

0170009-J0 Rev B

Acceptable bypass

input

Acceptable bypass

input

5.2.4  UPS Default Data and Special Function Execution

To run a self test or check default data, press the Function button to scroll to screen P1.

P1

Q1

R1

P2

Q2

R2

Press the DOWN button to scroll through the LCD screens and check the UPS settings. The LCD display

shows the following screens in sequence:
• Screen P1 (buzzer)
• Screen Q1 (self test)
• Screen R1 (Bypass Voltage)
• Screen S (Output Frequency Synchronized Window)
• Screen T (Inverter Output Voltage)
• Screen U1 (UPS Operation Mode)
• Screen V (Output Voltage Fine Tuning)