5 powering up the alpha micro secure – Alpha Technologies Micro Secure UPS User Manual
Page 20

017-220-J0 Rev B
18
5.5 Powering Up the Alpha Micro Secure
Make sure that the Line power is qualified but turned off and the batteries are fully charged.
Procedure
1. Turn on the Battery breaker.
2. Switch on the Line power and turn on the Input breaker.
3. Ensure the LEDs are working. See LED status table below.
4. When Line power is first applied, both LEDs illuminate and then only the green light remains on if the UPS is
in Line mode.
Table B — LED status description
LED Status
Description
GREEN OFF
The UPS inverter is turned off. Line power goes straight to the load.
GREEN ON
The UPS is turned on. Line power is provided to the load.
GREEN FLASHING
The UPS inverter is on. Backup battery power is provided to the load.
RED ON OR FLASHING
The UPS has a malfunction. See the troubleshooting table below.