Table Q —

Electrical Specifications

Parameter

Value

Input

Voltage (nominal), Vac

120 or 230 (optional 220).

Frequency, Hz, ±5%

60/50 (auto-frequency).

Current, A

2.0 @ 120Vac
1.0 @ 220/230Vac

Input circuit breaker

3.0A, 125Vac
1.5A, 230Vac

Output

Voltage (nominal), Vac

Auxiliary, Vac

120 or 230 ± 10%
24, –5% to +20%

Frequency, Hz, ±5%

60/50 (auto-frequency).

Current, A

4.20 @ 24Vac
0.83 @ 120Vac
0.43 @ 230Vac

Power, W/VA 100 total including auxiliary output

Waveform

Sine wave

Load Crest Factor

3:1 (load dependent)

Output Voltage Distortion

< 3% THD (resistive load)

Efficiency

Normal Mode

Backup (Inverter) Mode

> 85%
> 75%

Transfer Time, ms

AVR to Backup

Backup to AVR

5 (Typical)
3 (Typical)

Line Qualification Time, s 3

Battery String Voltage

24

Battery Charger Current

(Factory default, A)

3

Battery Charger Temperature

Compensation

-5mV / °C / Cell (factory default), user adjustable to -2.5, -4, -5 and -6mV / °C / Cell
via RS-232 connection.

Battery size

Standard: 4 x 9 AHr

Other

Battery circuit breaker

15A