12. Emergency Shutdown Procedure

The Alpha Micro Secure UPS contains more than one live circuit. In an emergency, line power may be discon-

nected at the UPS’s input, but AC power can still be present at the output.

1. Switch OFF the input circuit breaker.
2. Switch OFF the battery circuit breaker.
3. Disconnect the AC input power.
4. Disconnect the internal battery string.