6.6.3 Types of Trigger

There are 3 types of trigger:

Edge trigger
When the user input changes from one state to the other, the Alpha Micro Secure is triggered to perform Action

#1. If the level is set to High, the action will be triggered by a Low to High edge (leading edge). If the level is set

to Low, the action will be triggered by the High to Low edge (falling edge).

Low to High

edge trigger

User input

Action #1

Action #1

(a) Level = High
User Input = Low to High, Action #1 is triggered
User Input = High to Low, no action triggered

High to Low

edge trigger

User input

Action #1

Action #1

(b) Level = Low
User Input = High to Low, Action #1 is triggered
User Input = Low to High, no action triggered

Figure 47 — Edge Trigger

Level Toggle
When the Level is set to High, the Alpha Micro Secure is triggered to perform the other action when the user

input changes from Low to High. If the input then changes from High to Low, Action #2 will be triggered. In other

words, a level change in the user input will trigger an action toggle between Action #1 and #2.

Action #1

Action #1

Action #2

Action #2

User input

(a) Level = High
User Input = Low to High, Action #1 is triggered
User Input = High to Low, Action #2 is triggered

Action #2

Action #2

Action #1

Action #1

User input

(b) Level = Low
User Input = High to Low, Action #1 is triggered
User Input = Low to High, Action #2 is triggered

Figure 48 — Level Trigger