3. RS-232 HyperTerminal – the Temperature trigger function can be assigned to any available dry contacts as

described in "Programming the Dry Contacts" (e.g. c1=11, where 11 is the assigned index for the Temperature

trigger function.)

After establishing an RS-232 connection with the Alpha Micro Secure at the HyperTerminal screen prompt,

type Temp and press Enter to display the current temperature setting Alpha Micro Secure returns *temp=20).

To change the value to +35°C, type temp=35 and press Enter. The Alpha Micro Secure returns *temp=35 as

confirmation.

Figure 24 — Temperature trigger function via HyperTerminal

Programmable Dry Contact Time of Day Action
You can assign a dedicated timer to a dry contact. Upon entering the Inverter operating mode, the timer is acti-

vated and begins to count down from a user defined value. When the timer reaches zero, the programmed dry

contact relay will be activated (Status = ON).

 Inverter
mode
entered

 Dry contact
activates when timer
counts down to zero

 Timer
starts to
count down

Microprocessor

Figure 25 — Programmable Timer Operation