5.5 Powering Up the Alpha Micro Secure

Make sure that the Line power is qualified but turned off and the batteries are fully charged.

Procedure

1. Turn on the Battery breaker.

2. Switch on the Line power and turn on the Input breaker.

3. Ensure the LEDs are working. See LED status table below.

4. When Line power is first applied, both LEDs illuminate and then only the green light remains on if the UPS is

in Line mode.

Table B — LED status description

LED Status

Description

GREEN OFF

The UPS inverter is turned off. Line power goes straight to the load.

GREEN ON

The UPS is turned on. Line power is provided to the load.

GREEN FLASHING

The UPS inverter is on. Backup battery power is provided to the load.

RED ON OR FLASHING

The UPS has a malfunction. See the troubleshooting table below.