1 Introduction

1.1

Scope of the Manual

This instruction manual explains the features, installation, startup and maintenance of the INEX 100A STS
Module and MBS+PDU.

NOTE: Images contained in this document are for illustrative purposes only and may not exactly match your installation.

1.2 Product

Overview

The STS (Static Transfer Switch) module increases system reliability by automatically switching between the
inverter output and the AC mains. By setting up the priority of operation mode, users can change the system
status of “on line mode” or “off line mode”. The on line mode will keep the input power provided by inverter line
and when inverter fails, the line will switch to AC utility line. In off line mode, the system power is always
connected to the AC utility line and will switch to inverter power line when AC utility fails. The transfer time is less
than 1/4 cycle which can avoid the power interruption. The reliable performance of the STS module can provide
the maximum protection to the connected telecommunication equipment against possible damage caused by the
system power failure.

STS Module Features:

• Small footprint and weight

• Universal input range

• Hot-swap replacement in shelf (w/ MBS option)

• Back-feed protection

• Redundant fan design

• Fast transfer time, typically less than 1/4 cycle

• Low audible noise <55dBa

• No cross connect

• Optional maintenance bypass switch function

• Operation Priority Setup of transfer side by setting in Control Module

Figure 1–INEX 100A STS Module and MBS+PDU