Voltage and frequency range, 5 voltage and frequency range – Alpha Technologies INEX 100A STS Module and MBS+PDU User Manual

Page 15

Advertising
background image

Argus Technologies Ltd.

019-061-C0 Rev A WC

Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved.

Page 5 of 26

1.5

Voltage and Frequency Range

The STS module has two voltage inputs and one voltage output. The two inputs are Mains voltage and Inverter
voltage, and the output is System (output) voltage. STS will detect Mains voltage and Inverter voltage in order to
decide system’s supply mode when system is running. If both Mains and Inverter exist at the input, Mains has
priority to decide the operation status of system; in other words, STS will first consider Mains status to decide
system’s running voltage and frequency. Following the confirmation of voltage and frequency, the over/under
voltage and over/under frequency is set as follows:

120Vac

230Vac

Default Voltage

110V/115V/120V

208V/220V/230V/240V

Active 138Vac

276Vac

Over Volt

Recovery 134Vac

268Vac

Active 89Vac

176Vac

Under Volt

Recovery 93Vac

184Vac

Table A–Voltage default levels

System Frequency

60Hz

50Hz

Frequency High Threshold

61.5Hz

51.25Hz

Frequency High Back

61.2Hz

51Hz

Frequency Low Threshold

58.5Hz

48.75Hz

Frequency Low Back

58.8Hz

49Hz

Table B–Frequency default levels

The STS will transfer to the auxiliary source if the priority input voltage exceeds a preset value. The over/under
voltage limit can be set through controller, as shown on the following table. Users can set any value that is in the
valid range. STS won’t accept data that is out of the valid range; for example, you can set over volt point between
117~127 for 110V system, but the data that greater than 127 or less than 117 won’t be accepted. The valid range
is determined by the rated voltage sent to STS by inverter, as 110V, 115V, 120V (shown in the table).

120Vac

230Vac

Adjustable Range

110V

115V

120V

208V

220V

230V

240V

Adjustable
Range

117~127 122~132 127~138 220~240 233~252 244~264 254~276

Over Volt

Default
Value

127 132 138 240 252 264 276

Adjustable
Range

89~105 93~110 100~114 176~198 176~209 185~218 193~228

Under Volt

Default
Value

89 93 100 176 176 185 193

Table C–Inverter/System factory defaults


NOTE: If the STS has never been set for over/under voltage through the controller, then it will set the default value as

shown on Table C. Once the over/under volt points are set through the controller, the values will be saved to
EEprom, and it will remain in effect until resetting happens; except that, the next time when STS powers on, the
Mains/Inverter voltage changes from 120V system to 230V system or 230V to 120V.